Always set the warning time to a time shorter than any Alarm group restriction
disarmed time.
See 15-Alarm group restrictionson page 115 and AG restriction 1 disarmed
timeon page 62.
Disarmed alarm delay time
Disarmed Alm Delay Time Set To (Sec). 60
Time:
Determines the delay time (0 to 255 seconds) before an alarm from a delayed
disarmed alarm is reported to the central station. The delay time is ignored if
another delayed zone type has already been activated.
Note: The delay is available for zone types 8, 11, 22 and 40. See 1-Zone
databaseon page 7 for more information.
Suspicion time
Suspicion Time Is Set To (Sec). 15
Time:
The suspicion time is the length of time that a camera continues to operate after
a suspicion zone type has switched to normal state. The zone types that use this
record are 7, 40, and 47.
The suspicion time is available for zone types 7, 40 and 47. See 1-Zone
databaseon page 7 for more information.
Service time available
Service Time Is Set To (Min). 30
Time:
User menu 17 can be used to give access to service technicians. The alarm
group for the technician needs timezone 25 to be assigned. When a user enables
the service technician, timezone 25 will be valid during the service time (0 to
255 min).
Note: See 5-Alarm groupson page 50, 13-Timezoneson page 111, and
Advisor Master Manager Manual.
Local alarm reminder time
Local Alarm Reminder Time (Min). 5
Time:
The time that can elapse between acknowledging a local alarm and a re-alarm
occurring, including the audible alert (if the cause of the local alarm is not fixed).
Note: See 2-Area databaseon page 28, and Advisor Master Manager Manual,
“Local alarms, for further information