70 Advisor Master Programming Guide
7-System options
Program options common to the complete system.
Configuring system options
Areas selected for total disarm
16
Disarm Areas:
24-hour zone types (Disarmed Alarm or Firedoor) can be completely disarmed
using this menu. If the areas entered here are disarmed, 24-hour zone types are
inhibited. For best functionality, assign a common area to the 24-hour zone type
(its own area and the area programmed here). Disarm the programmed area to
disable the zone(s).
For example:
Zone 6 is a vault sensor in a vault. It is programmed as zone type 5 (24 hour)
and is assigned to areas 1 and 16. Area 16 is programmed for total disarm.
When servicing the vault, area 16 will be disarmed. From that moment on until
area 16 is armed again, zone 6 will be disabled (except for tamper alarms). Now
the following can occur:
Area 1
Area 16
Zone 6 behaviour
Armed
Armed
normal operation (as programmed zone type)
Disarmed
Armed
normal operation (as programmed zone type)
Armed
Disarmed
Zone disabled (except for tamper)
Disarmed
Disarmed
Zone disabled (except for tamper)
Note: When using this option, make sure the areas programmed for total disarm
can only be disarmed under correct conditions.
Film low level
Film Low Is Set To 0800
Film Level:
The film level number programmed is the film frame count. When this frame
count is reached, a film low is reported to the central station. Used for still video
or photo-cameras.
Note: Relates to zone types 23-26 and 36-39 (camera count). See 1-Zone
databaseon page 7.