Installation guide

78 Advisor Master Programming Guide
Press 0 to skip further options and leave system options.
See also Advisor Master Manager Manual for more information on users and
user flags.
Delayed disarmed alarm lockout
NO-Delayed Disarmed Alm Lockout
*-Change 0-Skip
This is only applicable to latching delayed disarmed alarms. If set to Yes, an
alarm can only be cancelled if the zone is in normal state. Therefore a latching
disarmed alarm is locked out until the alarm device is taken out of its latched
state (reset).
Yes: Delayed disarmed alarms are locked out until the alarm device is reset (and
the zone has switched to normal state).
No: Normal operation. Delayed disarmed alarms are not locked out.
Press 0 to skip further options and leave system options.
Zone expansion fitted
NO-Zone Expansion Fitted
*-Change 0-Skip
Indicate if zone expanders (ATS1202) are fitted on the control panel (not
applicable for expansion in DGPs).
Yes: Zone expanders are fitted on the control panel. The additional zone
numbers are 17 to 32.
No: No zone expanders fitted.
Press 0 to skip further options and leave system options.
See Advisor Master Installation Guide for information on fitting zone expanders
on the control panel.
Inhibit zone tamper
NO-Inhibit zone tamper
*-Change 0-Skip
Zone tampers in default programming will be inhibited when a zone is inhibited.
Yes: When a zone is inhibited, also the tamper is inhibited. No tamper alarm will
occur anymore.
No: An inhibited zone will only have inhibited alarms. Tamper alarms will still
occur.
Press 0 to skip further options and leave system options.