Advisor Master Programming Guide 79
Report multiple alarms
NO-Report Multiple Alarms In Zone
*-Change 0-Skip
The system is able to report multiple alarms that occurred in a zone (depending
on the reporting format).
Yes: Report multiple alarms as a separate alarm for each alarm that occurs.
No: Only report the first alarm. Every next alarm that occurs will not be reported.
Press 0 to skip further options and leave system options.
Report multiple restores
NO-Report Each Restored Multiple Alarm
*-Change 0-Skip
The system is able to generate a restore for each alarm being reported, even for
multiple alarms in a zone.
Yes: Report a restore for every alarm that occurred.
No: Report only one restore for every zone that generated an alarm.
Press 0 to skip further options and leave system options.
Engineer reset for system alarms
NO-Engineer Reset for System Alarms
*-Change 0-Skip
If an engineer reset is required on system alarms, set this option to Yes. A user
can not arm any area until an engineer reset has been performed.
Yes: After a system alarm, an engineer reset is required.
No: No engineer reset required.
Press 0 to skip further options and leave system options.
How to perform an engineer reset
Whenever an engineer reset is required, and User can do engineering reset
option on page 80 is set to No, only the installer can perform the Engineering
reset via Installer Menu (19/51).
Engineer Reset?
*-Reset 0-Skip
Whenever an engineer reset is required, and “User can do engineering reset
option on page 80 is set to Yes, the panel will display a 4-digit code. This code is
a reference to a special code that can be found in the Titan software package
(menu control) or received from your local distributor.