HRV / ERV INSTALLATION AND OPERATING INSTRUCTIONS Superior Series model: RHRV-S100A Aluminum Core RHRV-S100P Polypropylene Core RERV-S100 Enthalpy Core ® ® 2100 CERTIFIED C US Project Condo Unit Project Series model: model: RHRV-C100A RHRV-P100A Aluminum Core Aluminum Core RHRV-C100P RHRV-P100P Polypropylene Core Polypropylene Core RERV-C100 RERV-P100 Enthalpy Core Enthalpy Core Economy Series model: RHRV-E100A Aluminum Core 790 Rowntree Dairy Road, Woodbridge, ON Canada L4L 5V3
IMPORTANT SAFETY INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS ! WARNING ! TO REDUCE THE RISK OF FIRE, ELECTRIC SHOCK OR INJURY, OBSERVE THE FOLLOWING: 1. Read all the instructions carefully before installation, operation or maintenance of the unit. Failure to comply with instructions could result in personal injury and/or property damage. 2.
Parts List 1 Superior Series 1 model: RHRV-S100A 14 2 Aluminum Core RHRV-S100P 3a 13 Polypropylene Core 2 RERV-S100 3 Enthalpy Core 4 12 15 5 6 *Optional Parts: 12a 5 7 8 9 10 6 11 19 * * * 17 * RHRV-S100A RHRV-S100P RERV-S100 QTY. QTY. QTY.
Parts List 2 Project Condo Unit 1 model: 3a RHRV-C100A Aluminum Core 11 RHRV-C100P 8 Polypropylene Core 2 13 4 RERV-C100 Enthalpy Core 12a 2 12 14 3 10 *Optional Parts: 9 5 6 7 5 15 * 16 * 6 18 * 17 * RHRV-C100A RHRV-C100P RERV-C100 12a 13 14 15* 9315 014043C 9312 9313 9314 9358 9326 Temperature Sensor 5" Polypropylene Backdraft Damper 014043 9317 Blower - Supply / Exhaust 9319 Adjustable Door Latch Drain Spout Assembly 9320 9321 Core locking Bracket 014016 Nut 9322 Safety
Parts List 3 Project Series 1 model: RHRV-P100A 12a Aluminum Core 3a RHRV-P100P 2 Polypropylene Core 3 8 RERV-P100 11 Enthalpy Core 12 13 4 14 2 5 *Optional Parts: 6 5 7 9 18 Reference 1 2 Description 15 * 16 * 10 * 17 * RHRV-P100A RHRV-P100P RERV-P100 QTY. QTY. QTY. 1 2 1 n/a n/a 2 1 2 1 1 2 1 1 1 1 2 1 2 n/a 1 n/a 2 1 2 1 1 2 1 1 1 1 2 1 2 n/a n/a 1 2 1 2 1 1 2 1 1 1 1 2 9328 1 Set 1 Set 1 Set 011136 4 4 4 Part no.
Parts List 4 Economy Series 1 model: RHRV-E100A Aluminum Core 2 RHRV-E100P 3a Polypropylene Core 3 RERV-E100 Enthalpy Core 9 4 10 2 *Optional Parts: 5 6 7 14 Reference 1 2 4 8 * Description 13 * 12 * RHRV-E100A RHRV-E100P RERV-E100 QTY. QTY. QTY. 1 2 1 n/a n/a 2 2 1 2 1 1 1 2 n/a 1 n/a 2 2 1 2 1 1 1 2 n/a n/a 1 2 2 1 2 1 1 9328 1 Set 1 Set 1 Set 011135 4 4 4 Part no. 3a 4 5 6 7 8 HRV / ERV - Lid, Pan Assembly 9315 Polypropylene Collar 5” Dia.
Wiring Diagram (Superior, Project Series and Project Condo Unit) 5 d) CONTROL BOARD: Optional Accessories (Not Supplied) a) Timer Switch (TC100) b) Wall Switch c) Dehumidistat d) Time Delay Switch e) Master On/Off Switch for HRV/ERV f ) Light or b) b) c) e) Hi Hi On Low Low a) YEL RED Note: Same power source should be used for wall switch and HRV / ERV GND FAN HIGH VOLTAGE C Speed Contact C N0 NC Ext.
Wiring Diagram (cont’d) 6 Furnace / Fan-Coil / Heat Pump Interlock: Standard Interlock Wiring THERMOSTAT TERMINALS W TWO WIRE heating only R G Y FOUR WIRE W L0/HI Speed HV Input R Remote 0n/0ff HV C N0 NC C Speed Contact +5 C DAT G HIGH VOLTAGE Ext.
HRV and ERV Typical Installations 7 Typical Installations for House Fully Ducted System (for Superior series only) This is a stand alone HRV/ERV system which is not connected to a force air system. Stale air is drawn from key areas of the home (bathroom, kitchen) while fresh air is supplied to main living areas. 2 Single Vents SVE-50 and SVI-50 Shown, 5 ft.
HRV and ERV Typical Installations (cont’d) 8 HORIZONTAL Note: • 30” clearance is recommended for cleaning of the core/servicing the unit. • Dampers are installed for horizontal installation. For vertical installation both dampers have to be turned so they can open properly and close when there is any backdraft. • Make sure no screw will interfere the function of the backdraft dampers.
HRV and ERV Typical Installations (cont’d) 9 Typical Installations of Single Vents & Access door CAULKING GRILLE Metal Clamp - 3 SIDES ONLY, NOT ON BOTTOM Insulation Intake Exhaust Duct Insulation Wallbox CAULKING WALLBOX - CAULK WALLBOX TO STRUCTURE ON ALL 4 SIDES Grille Backdraft Damper Minimum 5 Feet (1” Thick) Minimum 5 Feet Insulation Access Door Note: Fresh air intake and supply duct must be totally insulated. Exhaust duct must be 5 feet insulated.
Air Flow Balancing 10 Balancing Procedure It is required to have balanced air flows in an HRV/ERV. The volume of air brought in from the outside must equal the volume of air exhausted by the unit while running at normal speed. If the air flows are not properly balanced, then: • The HRV/ERV may not function at its maximum efficiency • A negative or positive air pressure may occur in the house or condo • The unit may not defrost properly Prior to balancing, ensure that: 1. 2. 3. 4. 5.
Air Flow Balancing (cont’d) 11 Note:(Option #2)- Only for “superior” series DUCT DIAM. 5" 6" 7" *For balancing, extension box cover plate is provided with 3 holes on supply side and 3 holes on exhaust side. *Do not use pitot tube to open holes in the insulation as it may block/damage the pitot tube. *Take 3 readings on each hole and average all 9 readings for supply and same for exhaust. Opening area: 0.136 sq.ft. *After finish balancing, plug all six holes with plastic plugs provided with the unit.
Maintenance (cont’d) 12 Annual Maintenance Repeat steps 1 to 5 from the previous section and continue with the following steps: 1.
Troubleshooting (cont’d) 13 2. Senses cold air from Supply - Exhaust hood outside the house is blocked - HRV/ERV airflow improperly balanced - outdoor temperature is extremely cold - remove the blockage and clean the hood - have contractor balance the unit - placement of furniture or closed doors is restricting the movement of air in the home - install a duct heater 3.
Climate Zone 14 Select HRV/ERV for your Climate Zone HRVs are recommended for colder climates. ERVs are designed for warm-humid climates with long cooling seasons. Severe Conditions Pacific Conditions Moderate Conditions Dry Climate High Humidity U.S. Department of Energy climate zones map 790 Rowntree Dairy Road, Woodbridge ON, Canada L4L 5V3 Tel: 905-851-6701 • Fax: 905-851-8376 • info@reversomatic.com Toll Free: 1.800.810.3473 (Canada) • 1.866.890.6457 (U.S.A.) www.reversomatic.