17. Clear SOC relay
When the state-of-charge percentage has risen above this value, the relay will open (after a
delay, depending on setting 14 and/or 15). This value needs to be greater than the previous
parameter setting. When the value is equal to the previous parameter the state-of-charge
percentage will not close the relay.
Default Range Step size
90% 0 99% 1%
______________________________________________________________
18. Low voltage relay
When the battery voltage falls below this value for more than 10 seconds the relay will
close.
19. Clear low voltage relay
When the battery voltage rises above this value, the relay will open (after a delay,
depending on setting 14 and/or 15). This value needs to be greater than or equal to the
previous parameter.
20. High voltage relay
When the battery voltage rises above this value for more than 10 seconds the relay will
close.
21. Clear high voltage relay
When the battery voltage falls below this value, the relay will open (after a delay, depending
on setting 14 and/or 15). This value needs to be less than or equal to the previous
parameter.
BMV-700 / BMV-702 / BMV 712 Smart
Default Range Step size
0V 0 95V 0,1V
BMV-700H
Default Range Step size
0V 0 384V 0,1V
______________________________________________________________
22. Low starter voltage relay - 702 and -712 only
When the auxiliary (e.g. starter battery) voltage falls below this value for more than
10 seconds the relay will be activated.
23. Clear low starter voltage relay - 702 and -712 only
When the auxiliary voltage rises above this value, the relay will open (after a delay,
depending on setting 14 and/or 15). This value needs to be greater than or equal to the
previous parameter.
24. High starter voltage relay - 702 and -712 only
When the auxiliary (e.g. starter battery) voltage rises above this value for more than
10 seconds, the relay will be activated.