MG2S Spec Sheet

6
BLOWER PERFORMANCE - Top Return
MODEL NUMBER
MOTOR SWITCH
SETTINGS
(0 =OFF,1 =ON)
COOLING HEATING
EXTERNAL STATIC PRESSURE (IN.W.C.) EXTERNAL STATIC PRESSURE (IN.W.C.)
0.2 0.3 0.4 0.5 0.2 0.3 0.4 0.5
1/5 2/6 3/7 4/8 CFM CFM CFM CFM CFM RISE CFM RISE CFM RISE CFM RISE
MG2S-045T*
0 0 0 0 872 831 797 745 872 46 831 48 797 50 745 54
1 0 0 0 924 888 855 809 924 43 888 45 855 47 809 49
0 1 0 0 1005 969 939 899 1005 40 969 41 939 43 899 44
1 1 0 0 1076 1043 1014 972 1076 37 1043 38 1014 39 972 41
0 0 1 0 1155 1122 1078 1046 1155 35 1122 36 1078 37 1046 38
1 0 1 0 1220 1187 1158 1126 1220 33 1187 34 1158 35 1126 36
0 1 1 0 1269 1230 1199 1164
1 1 1 0 1321 1290 1251 1218
0 0 0 1 1399 1360 1325 1293
1 0 0 1 1448 1423 1382 1347
0 1 0 1 1495 1463 1427 1390
1 1 0 1 1531 1490 1457 1424
0 0 1 1 1564 1534 1501 1464
1 0 1 1 1611 1576 1543 1510
0 1 1 1 1645 1609 1583 1547
1 1 1 1 1683 1653 1624 1594
MG2S-060T*
0 0 0 0 872 831 797 745 872 61 831 64 797 67 745 72
1 0 0 0 924 888 855 809 924 58 888 60 855 62 809 66
0 1 0 0 1005 969 939 899 1005 53 969 55 939 57 899 59
1 1 0 0 1076 1043 1014 972 1076 50 1043 51 1014 53 972 55
0 0 1 0 1155 1122 1078 1046 1155 46 1122 48 1078 49 1046 51
1 0 1 0 1220 1187 1158 1126 1220 44 1187 45 1158 46 1126 47
0 1 1 0 1269 1230 1199 1164
1 1 1 0 1321 1290 1251 1218
0 0 0 1 1399 1360 1325 1293
1 0 0 1 1448 1423 1382 1347
0 1 0 1 1495 1463 1427 1390
1 1 0 1 1531 1490 1457 1424
0 0 1 1 1564 1534 1501 1464
1 0 1 1 1611 1576 1543 1510
0 1 1 1 1645 1609 1583 1547
1 1 1 1 1683 1653 1624 1594
MG2S-072T
0 0 0 0 885 848 804 764 885 72 848 75 804 80 764 84
1 0 0 0 944 901 862 816 944 68 901 71 862 74 816 78
0 1 0 0 1020 976 940 906 1020 63 976 66 940 68 906 71
1 1 0 0 1087 1055 1019 985 1087 59 1055 61 1019 63 985 65
0 0 1 0 1161 1132 1089 1060 1161 55 1132 57 1089 59 1060 60
1 0 1 0 1225 1195 1164 1137 1225 52 1195 54 1164 55 1137 56
0 1 1 0 1265 1239 1204 1175 1265 51 1239 52 1204 53 1175 54
1 1 1 0 1330 1299 1265 1228 1330 48 1299 49 1265 51 1228 52
0 0 0 1 1388 1353 1320 1289
1 0 0 1 1447 1413 1382 1346
0 1 0 1 1489 1454 1423 1388
1 1 0 1 1513 1484 1452 1420
0 0 1 1 1556 1523 1492 1459
1 0 1 1 1599 1566 1534 1502
0 1 1 1 1639 1609 1578 1547
1 1 1 1 1670 1651 1613 1583
Greyed out blower speeds do not meet FER efficiency requirements and should not be used.