Revolve RPH Installation Manual

Table Of Contents
10
MODEL
NUMBER
MOTOR
TAP
EXTERNAL STATIC PRESSURE DROP (IN WC)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
024K
T1* 930 875 818 761 704 645 585 525
T2 1158 1119 1076 1028 977 921 861 796
T3** 1308 1271 1230 1185 1136 1084 1027 967
T4 1440 1406 1368 1326 1281 1232 1179 1122
T5 1622 1587 1550 1510 1467 1422 1373 1323
030K
T1 930 875 818 761 704 645 585 525
T2* 1158 1119 1076 1028 977 921 861 796
T3** 1308 1271 1230 1185 1136 1084 1027 967
T4 1440 1406 1368 1326 1281 1232 1179 1122
T5 1622 1587 1550 1510 1467 1422 1373 1323
036K
T1 1158 1119 1076 1028 977 921 861 796
T2 1308 1271 1230 1185 1136 1084 1027 967
T3* 1366 1332 1291 1245 1192 1132 1067 995
T4** 1518 1481 1442 1400 1355 1307 1256 1202
T5 1686 1644 1601 1556 1509 1460 1410 1358
042K
T1 1339 1297 1254 1210 1166 1121 1075 1029
T2** 1459 1422 1383 1342 1300 1256 1211 1164
T3* 1569 1530 1491 1451 1410 1368 1325 1282
T4 1709 1674 1638 1601 1562 1521 1479 1436
T5 1820 1785 1748 1710 1671 1630 1589 1545
048K
T1** 1418 1385 1351 1316 1279 1242 1203 1163
T2 1530 1500 1467 1433 1396 1358 1318 1275
T3* 1679 1645 1611 1576 1541 1505 1469 1432
T4 1787 1757 1726 1693 1658 1621 1582 1542
T5 2006 1973 1939 1905 1870 1834 1798 1761
060K
T1 1147 1102 1053 1001 945 886 824 758
T2 1645 1602 1557 1512 1466 1420 1372 1324
T3* 2131 2090 2047 2001 1954 1906 1855 1802
T4** 2182 2144 2104 2063 2020 1976 1930 1882
T5 1921 2014 2084 2129 2152 2150 2125 2077
NOTES:
* Denotes air flow setting for cooling & heating
** Denotes air flow setting for electric heating (10 KW)
Airflow performance is with a dry coil.
Table 2. Airflow Data
Table 3. Control Board Status Indicators
STATUS INDICATOR STATUS TYPE DIAGNOSTIC DESCRIPTION
C1
Operating Status Cooling, 1st Stage
H1
Operating Status Heating, 1st Stage
SC
Operating Status Anti Short Cycle Timer
0S
Operating Status Defrost
_.
Operating Status Power on, no call for operation
01
Fault Pressure Switch, low
02
Fault Pressure Switch, high
03
Fault Temperature Sensor, Ambient
04
Fault Temperature Sensor, Coil
05
Fault Board
0F (FLASHING)
Input Error
Forced defrost - test short applied longer
than 11 minurtes