Installation - Gas Pressure Regulator Kit Manual

Mfg #124760, Page 1
APPLIES TO: Model Series ADF/ADFH;
RGB/RGBL/RPB/RPBL;
PGBL; SSCBL; and DFA
Option CZ,
Gas Pressure
Regulator Kits
INSTALLATION FORM RZ-NA-I-OPT-GR
Obsoletes Form RGM 400-GR
Description
The maximum gas supply pressure to the applicable Reznor Models is 1/2 psi (14" w.c.). Option CZ gas pressure regulator kits are
designed to regulate the gas pressure downward if the gas supply pressure is greater than 1/2 psi but less than or equal to 5 psi.
Depending on the pipe size, there are four regulator kits.
The gas regulators in these kits are the lock-up type and comply with codes using this specification. Under static conditions (no gas
flow), a lock-up type regulator will allow the outlet pressure to rise slightly above the adjusted pressure but will still be low enough
to protect the downstream gas controls. The regulators have an adjustable outlet gas range of 4" to 12" w.c. and are suitable for either
natural or propane gas.
Installation Instructions
NOTE: Pipe joint compound (pipe dope) must be resistant to the action of liquefied petroleum gas or any other chemical constituents
of the gas being supplied.
Maxitrol Regulator Specifications
Maxitrol Model 210DZ, 1" 210DZ, 1-1/4" 210EZ, 1-1/2" 210EZ, 2"
Reznor P/N 124254 170645 124255 170647
Size 1" x 1" NPT 1-1/4" x 1-1/4" NPT 1-1/2" x 1-1/2" NPT 2" x 2" NPT
Housing High strength aluminum alloy High strength aluminum alloy High strength aluminium alloy High strength aluminium alloy
Ambient Range -40°F to 200
°
F -40
°
F to 200
°
F -40
°
F to 200
°
F -40
°
F to 200
°
F
Maximum Pressure 5 psi 5 psi 5 psi 5 psi
Emergency Exposure 25 psi (inlet side only) 25 psi (inlet side only) 25 psi (inlet side only) 25 psi (inlet side only)
Pressure Tap Both inlet & outlet (plugged) Both inlet & outlet (plugged) Both inlet & outlet (plugged) Both inlet & outlet (plugged)
Vertical Vent 3/8" NPT 3/8" NPT 3/4" NPT 3/4" NPT
Flow Rate Capacity See TABLE 1 on page 2 See TABLE 2 on page 2 See TABLE 3 on page 2 See TABLE 4 on page 2
WARNING: Do not install these regulator kits if gas supply is greater than 5 psi. A field-supplied
regulator with adequate capacity is required.
Option Kits include:
1. Turn off the gas supply.
2. Install the Regulator
The gas regulator must be in an upright position. Exterior to
the heater cabinet, connect the regulator into a horizontal sec-
tion of the gas supply line.
Pipe Size 1" 1-1/4" 1-1/2" 2"
Option No. CZ1 or CZ4B CZ2 or CZ4D
CZ4A CZ4C
Package P/N 124258 170644 124259 170646
Code Components Qty P/N P/N P/N P/N
1 Maxitrol Regulator 1 124254 170645 124255 170647
(see model and specifications below)
2 Hex Bushing (black iron) 1 8643 8643 124256 124256
3/8" x 1/8" 3/8" x 1/8" 3/4" x 1/8" 3/4" x 1/8"
3 1/8" x 2-1/2" Brass Nipple 3 107122 107122 107122 107122
4 1/8", 90
°
Brass Elbows 2 124257 124257 124257 124257
5 Insect Screen Assembly 1 96793 96793 96793 96793
2
4
5
3
1
®