FIGURE 15 - Venting Arrangement with Vent
Run (no ceiling)
FIGURE 14 - Venting Arrangement with Vent Run
and through a Ceiling
FIGURE 16 - Venting Arrangement
without Vent Run
9. If the unit heater is installed in a space served by a large exhaust fan, be sure that
the exhaust fan does not affect the operation of the heater or the satisfactory vent-
ing of its products of combustion.
If a negative pressure exists, as evidenced by a downdraft, a factory-designed
mechanical motor driven venter (Option CA) should be installed. (The addition of
a power venter allows for horizontal venting and alters the venting requirements
including the vent pipe size and length. For additional installation information on an
optional power venter, refer to Paragraph 6.2.4. Complete information is included
in the venter package.)
In severe negative pressure conditions, makeup air equipment may be necessary.
6.2.2 Venting
Requirements (cont'd)
6. Mechanical
(cont'd)
6.2 Venting (cont'd)
Model Sizes 25/50 75 100 125 165/200 250/300 400
Vertical
Height of Vent
Vent Diameter
4" 5" 6" 7" 8" 10" 12"
Maximum Horizontal Run Length using Double Wall Type B Connector and Double-Wall Type B Vent
7 ft (2.1M) 2 ft .6M 6 ft 1.8M 6 ft 1.8M 6 ft 1.8M 6 ft 1.8M 6 ft 1.8M 6 ft 1.8M
9 ft (2.7M) 6 ft 1.8M 6 ft 1.8M 7 ft 2.1M 16 ft 4.9M 16 ft 4.9M 16 ft 4.9M 16 ft 4.9M
10 ft (3M) 8 ft 2.4M 10 ft 3M 16 ft 4.9M 20 ft 6.1M 20 ft 6.1M 20 ft 6.1M 20 ft 6.1M
15 ft (4.6M) 12 ft 3.7M 16 ft 4.9M 16 ft 4.9M 30 ft 9.1M 30 ft 9.1M 30 ft 9.1M 30 ft 9.1M
20 ft (6.1M) 16 ft 4.9M 20 ft 6.1M 30 ft 9.1M 30 ft 9.1M 30 ft 9.1M 30 ft 9.1M 30 ft 9.1M
30 ft (9.1M) 18 ft 5.5M 20 ft 6.1M 40 ft 12.2M 40 ft 12.2M 40 ft 12.2M 40 ft 12.2M 40 ft 12.2M
Maximum Horizontal Run Length using Single Wall Metal Pipe
6 ft (1.8M 2 ft .6M 2 ft .6M 2 ft .6M 2 ft .6M 2 ft .6M 2 ft .6M 2 ft .6M
8 ft (2.4M) 2 ft .6M 5 ft 1.5M 5 ft 1.5M 10 ft 3M 10 ft 3M 10 ft 3M 10 ft 3M
10 ft (3M) 2 ft .6M 5 ft 1.5M 10 ft 3M 15 ft 4.6M 15 ft 4.6M 15 ft 4.6M 15 ft 4.6M
15 ft (4.6M) 2 ft .6M 5 ft 1.5M 10 ft 3M 15 ft 4.6M 20 ft 6.1M 20 ft 6.1M 20 ft 6.1M
20 ft (6.1M) N.R. 10 ft 3M 15 ft 4.6M 20 ft 6.1M 20 ft 6.1M 20 ft 6.1M
Vent Run Length Table