2.2 Insulation Test
Measure EFMAs insulation resistance at each step using a megohmeter (Fig.
2.2) and record readings on the measures’table (this label is available at the
opening of the product).
IMPORTANT!
For the warranty to be valid, ll out the measures’ table and ensure that the
10 readings have been correctly noted.
A qualied electrician must measure the systems insulation resistance as follows:
• Use a calibrated megohmeter only;
• Measure insulation resistance at the free end of the cold lead, between the phase
conductor and ground;
cold lead
Fig. 2.2
CAUTION! Dangerous Test
• Write the reading in the measures’table;
• is reading must be over 1,000,000ohms;
• If the reading is under 1,000,000ohms, stop work and contact REZNORs technical
specialists at 1800695-1901.