Installation - Elec Heating User guide
10
Table 2c. Electrical Data - Packaged H/P - Q5 Units - 3 Phase, 60 Hertz
Model
Number
Allowable
Voltage
Range
Compressors
Outdoor
motors
(2) ea.
Indoor
Motor
Mult. Circ. “A” †
Single Circuit - Q5SN & H5HK kit
MCA MOP MCA MOP
Factory Drive Data:
Q5SN Min Max Qty RLA LRA FLA FLA No Heater Kit 9 kW 18 kW 30 kW 35 kW 9 kW 18 kW 30 kW 35 kW
-090 C 187 253 2 ea. 12.8 91 2.3 4.2 - 4.0 38 - 38 50 - 50 49 - 52 71 - 77 100 - 112 116 - 130 55 - 55 80 - 80 110 - 125 125 - 150
-090 D 414 506 2 ea. 6.4 46 1.2 2.0 19 25 28 40 56 65 30 45 60 70
-120 C 187 253 2 ea. 15.4 124 2.3 6.2 - 5.8 46 - 46 60 - 60 54 - 57 76 - 82 106 - 117 121 - 135 60 - 60 80 - 90 110 - 125 125 - 150
-120 D 414 506 2 ea. 7.4 59.6 1.2 2.9 22 25 30 42 58 67 35 45 60 70
High Static Drive Data:
-090 C 187 253 2 ea. 12.8 91 2.3 9.1 - 8.9 43 - 43 55 - 55 54 - 57 75 - 82 105 - 117 121 - 135 60 - 60 80 - 90 110 - 125 125 - 150
-090 D 414 506 2 ea. 6.4 46 1.2 4.4 22 25 30 42 59 68 35 45 60 70
-120 C 187 253 2 ea. 15.4 124 2.3 9.1 - 8.9 49 - 49 60 - 60 57 - 60 79 - 86 108 - 120 124 - 138 60 - 70 80 - 90 110 - 125 125 - 150
-120 D 414 506 2 ea. 7.4 59.6 1.2 4.4 24 30 31 44 60 69 35 45 70 70