Installation - Elec Heating User guide
11
Table 2d. Electrical Data - Packaged H/P - Q6 Units - 3 Phase, 60 Hertz
Model
Number
Allowable
Voltage
Range
Compressors
Outdoor
motors
(2) ea.
Indoor
Motor
Mult. Circ. “A” †
Single Circuit - Q6SP & H5HK kit
MCA MOP MCA MOP
Factory Drive Data:
Q6SP Min Max Qty RLA LRA FLA FLA No Heater Kit 9 kW 18 kW 30 kW 35 kW 9 kW 18 kW 30 kW 35 kW
-090 C 187 253 2 ea. 13.1 83.1 2.3 4.2 - 4.0 39 - 39 50 - 50 49 - 52 71 - 78 101 - 112 116 - 130 55 - 55 80 - 80 110 - 125 125 - 150
-090 D 414 506 2 ea. 6.1 41 1.2 2.0 19 20 27 40 56 65 30 45 60 70
-120 C 187 253 2 ea. 15.6 110 2.3 6.2 - 5.8 46 - 46 60 - 60 54 - 57 76 - 83 106 - 117 121 - 135 60 - 60 80 - 90 110 - 125 125 - 150
-120 D 414 506 2 ea. 7.8 52 1.2 2.9 23 30 30 43 59 68 35 45 60 70
High Static Drive Data:
-090 C 187 253 2 ea. 13.1 83.1 2.3 9.1 - 8.9 44 - 44 55 - 55 54 - 57 76 - 83 106 - 117 121 - 135 60 - 60 80 - 90 110 - 125 125 - 150
-090 D 414 506 2 ea. 6.1 41 1.2 4.4 21 25 30 42 58 67 35 45 60 70
-120 C 187 253 2 ea. 16.0 110 2.3 9.1 - 8.9 49 - 49 60 - 60 57 - 61 79 - 86 109 - 120 124 - 138 60 - 70 80 - 90 110 - 125 125 - 150
-120 D 414 506 2 ea. 7.8 52 1.2 4.4 25 30 32 44 60 69 35 45 70 70
Table 2d. Electrical Data - Packaged H/P - Q6 Units - 3 Phase, 60 Hertz
FLA = Full Load AmpsNotes: MCA = Minimum Circuit Ampacity C Series, Electrical unit data shown for 208V - 230V
RLA = Rated Load Amps MOP = Maximum Over-Current Protection D Series, Electrical unit data shown for 460V
LRA = Locked Rotor Amps
† When used with 917468 Dual Circuit Adapter Kit - See Table 2 for Multiple Circuit “B” data