Installation - Elec Heating User guide
8
Table 2a. Electrical Data - Package A/C - P4 Units
Unit
Model
Heater Kit Electrical Data
Multiple Circuits
Single Circuit Circuit A (Cooling) Circuit B (Heating)
Minimum
Circuit
Ampacity
Maximum
Over-Current
Rating
Minimum
Circuit
Ampacity
Maximum
Over-Current
Rating
Minimum
Circuit
Ampacity
Maximum
Over-Current
Rating
Model
Number
Rated
Volts
Phase Kw
(*)P4S(M/N)-090C
7.5 Ton Package A/C
208/230V, 3 Phase
No Kit - - - - - - - - - 42.2 60 - - - - - - - - - - - -
H5HK-009Q 208/240 3 9 42.2 60 - - - - - - - - - - - -
H5HK-018Q 208/240 3 17.4 60.2 70 42.2 60.0 52.3 60.0
H5HK-035Q 208/240 3 34.8 112.5 125 42.2 60.0 104.6 110.0
(*)P4S(M/N)-090D
7.5 Ton Package A/C
460V, 3 Phase
No Kit - - - - - - - - - 21.2 30 - - - - - - - - - - - -
H5HK-018S 480 3 18 30.9 40 21.2 30.0 27.1 30.0
H5HK-035S 480 3 34.8 56.2 60 21.2 30.0 52.3 60.0
(*)P4S(M/N)-120C
10 Ton Package A/C
208/230V, 3 Phase
No Kit - - - - - - - - - 61.3 90 - - - - - - - - - - - -
H5HK-009Q 208/240 3 9 61.3 90 - - - - - - - - - - - -
H5HK-018Q 208/240 3 17.4 63.7 90 - - - - - - - - - - - -
H5HK-035Q 208/240 3 34.8 116.0 125 61.3 90.0 104.6 110.0
(*)P4S(M/N)-120D
10 Ton Package A/C
460V, 3 Phase
No Kit - - - - - - - - - 27.2 40 - - - - - - - - - - - -
H5HK-018S 480 3 18 32.6 40 - - - - - - - - - - - -
H5HK-035S 480 3 34.8 57.8 60 27.2 40.0 52.3 60.0