Table 2b. Electrical Data - Packaged A/C - P6 Units - 3 Phase, 60 Hertz
Model
Number
Allowable
Voltage
Range
Compressors
Outdoor
motors
(2) ea.
Indoor
Motor
Mult. Circ. “A” † Single Circuit - P6SP & H5HK kit
MCA MOP MCA MOP
Factory Drive Data:
P6SP Min Max Qty RLA LRA FLA FLA No Heater Kit 9 kW 18 kW 30 kW 35 kW 9 kW 18 kW 30 kW 35 kW
-072 C 187 253 1 ea. 19 123 1.5 3.2 - 3.1 30 - 30 45 - 45 30 - 31 50 - 57 80 - 91
- n/a -
45 - 45 55 - 60 90 - 100
- n/a -
-072 D 414 506 1 ea. 9.7 62 0.8 1.5 16 20 17 29 46
- n/a -
20 30 50
- n/a -
-090 C 187 253 2 ea. 13.1 83.1 2.3 6.2 - 5.8 41 - 40 50 - 50 41 - 40 54 - 60 83 - 94 99 - 112 50 - 50 55 - 70 90 - 100 100 - 125
-090 D 414 506 2 ea. 6.1 41 1.2 2.9 19 25 19 31 47 56 25 35 50 60
-120 C 187 253 2 ea. 16.0 110 2.3 6.2 - 5.8 47 - 47 60 - 60 47 - 47 54 - 60 83 - 94 99 - 112 60 - 60 60 - 70 90 - 100 100 - 125
-120 D 414 506 2 ea. 7.8 52 1.2 2.9 23 30 23 31 47 56 30 35 50 60
Medium Static Drive Data:
-072 C 187 253 1 ea. 19 123 1.5 4.4 - 4.2 32 - 31 50 - 45 32 - 33 51 - 58 81 - 92
- n/a -
50 - 45 60 - 60 90 - 100
- n/a -
-072 D 414 506 1 ea. 9.7 62 0.8 2.1 16 25 18 30 46
- n/a -
25 35 50
- n/a -
-090 C 187 253 2 ea. 13.1 83.1 2.3 9.1 - 8.9 44 - 43 55 - 55 44 - 43 57 - 64 87 - 98 103 - 116 55 - 55 60 - 70 90 - 100 100 - 125
-090 D 414 506 2 ea. 6.1 41 1.2 4.4 21 25 21 33 49 58 25 35 50 60
-120 C
Not Applicable
-120 D
High Static Drive Data:
-072 C
Not Applicable
-072 D
-090 C 187 253 2 ea. 13.1 83.1 2.3 9.1 - 8.9 44 - 43 55 - 55 44 - 43 57 - 64 87 - 98 103 - 116 55 - 55 60 - 70 90 - 100 100 - 125
-090 D 414 506 2 ea. 6.1 41 1.2 4.4 21 25 21 33 49 58 25 35 50 60
-120 C 187 253 2 ea. 16.0 110 2.3 9.1 - 8.9 50 - 50 60 - 60 50 - 50 57 - 64 87 - 98 103 - 116 60 - 60 60 - 70 90 - 100 100 - 125
-120 D 414 506 2 ea. 7.8 52 1.2 4.4 25 30 25 33 49 58 30 35 50 60
Notes:FLA = Full Load Amps
RLA = Rated Load Amps
LRA = Locked Rotor Amps
MCA = Minimum Circuit Ampacity
MOP = Maximum Over-Current Protection
C Series, Electrical unit data shown for 208V - 230V
D Series, Electrical unit data shown for 460V
† When used with 917468 Dual Circuit Adapter Kit - See Table 2 for Multiple Circuit “B” data