Table 14
Table 13
Table 12
Airflow Data
Table 14. AirowSettings(CFM)&Rise(°F)forHeatingMode
MODEL NUMBER
HEATING INPUT
(BTUH)
HEATING OUTPUT
(BTUH)
HEATING
RANGE
HEATING RISE
RANGE (°F)
BLOWER
SIZE
MOTOR
(HP)
E24K080X
80,000 64,800 1025 - 1375
35-65 11X8 1/2
52,000 42,100 800 - 1050
E36K100X
100,000 81,000 1150 - 1500
40-70
11X8 1/2
65,000 52,650 875 - 1200
E48K120X
120,000 97,200 1550 - 2000
40-70
11X10 1
78,000 63,180 1200 - 1575
E60K120X
120,000 97,200 1550 - 2000
40-70
11X10 1
78,000 63,180 1200 - 1575
NOTE: CFM and Rise are independent of ESP in a variable speed blower.
Table 13. AirowSettingsforCoolingMode
2 TON CFM SETTINGS 3 TON CFM SETTINGS 4 TON CFM SETTINGS 5 TON CFM SETTINGS
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
COOLING
BLOWER
SELECTOR
SETTING
RECOMMENDED
AIRFLOW
(HIGH CFM)
(1) 5 6 7 8 (1) 5 6 7 8 (1) 5 6 7 8 (1) 5 6 7 8
0
0 0 0 0 650 1 0 0 0 0 900 0 0 0 0 0 1375 1 0 0 0 0 1500
0
0 0 0 1 680 1 0 0 0 1 935 0 0 0 0 1
4
TON
1400 1 0 0 0 1 1540
0
0 0 1 0 710 1 0 0 1 0 970 0 0 0 1 0 1425 1 0 0 1 0
5
TON
1580
0
0 0 1 1
2
TON
740 1 0 0 1 1 1005
0 0 0 1 1 1450
1 0 0 1 1 1620
0
0 1 0 0 770 1 0 1 0 0 1040 0 0 1 0 0 1475
1 0 1 0 0 1660
0 0 1 0 1
800
1 0 1 0 1 1075 0 0 1 0 1 1500 1 0 1 0 1 1700
0
0 1 1 0 830 1 0 1 1 0
3
TON
1110 0 0 1 1 0 1525 1 0 1 1 0 1740
0
0 1 1 1 860 1 0 1 1 1 1145 0 0 1 1 1 1550 1 0 1 1 1 1780
0
1 0 0 0 890 1 1 0 0 0
1180
0 1 0 0 0 1575 1 1 0 0 0 1820
0
1 0 0 1 920 1 1 0 0 1 1215 0 1 0 0 1 1600 1 1 0 0 1 1860
0
1 0 1 0 950 1 1 0 1 0 1250 0 1 0 1 0 1625 1 1 0 1 0 1900
0
1 0 1 1 980 1 1 0 1 1 1285 0 1 0 1 1 1650 1 1 0 1 1 1940
0
1 1 0 0 1010 1 1 1 0 0 1320 0 1 1 0 0 1675 1 1 1 0 0 1980
0
1 1 0 1 1040 1 1 1 0 1 1355 0 1 1 0 1 1700 1 1 1 0 1 2020
0
1 1 1 0 1070 1 1 1 1 0 1390 0 1 1 1 0 1750 1 1 1 1 0 2060
0
1 1 1 1 1100 1 1 1 1 1 1425 0 1 1 1 1 1800 1 1 1 1 1 2100
NOTES: Dip switch positions - 0 = OFF 1 = ON
1. Switch (1) selects blower program in conjunction with motor horsepower. 0 = 2 or 4 Ton, 1 = 3 or 5 Ton.
2. Recommended CFM’s (factory settings) are highlighted in bold.
Table 12. Nominal Heating Airflow Rates & Temperature Rises (° F)
HEATING
BLOWER
SELECTOR
SETTING
2 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
3 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
4 TON CFM SETTINGS
HEATING
BLOWER
SELECTOR
SETTING
5 TON CFM SETTINGS
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
LOW
HEAT
HIGH
HEAT
64,800 80,000 81,000 100,000 97,200 120,000 97,200 120,000
(1) 2 3 4 CFM RISE CFM RISE (1) 2 3 4 CFM RISE CFM RISE (1) 2 3 4 CFM RISE CFM RISE (1) 2 3 4 CFM RISE CFM RISE
0 0 0 0 800 50 1025 59 1 0 0 0 875 56 1150 66 0 0 0 0 1200 54 1550 57 1 0 0 0 1200
54
1550 57
0 0 0 1 850 48 1075 57 1 0 0 1 925 53 1200 63
0 0 0 1 1250 50 1650 54 1 0 0 1 1250 50
1650 54
0 0 1 0 875 46 1125 55 1 0 1 0 975 50 1300 58
0 0 1 0 1300 47 1750
52 1 0 1 0 1300 47 1750 52
0 0 1 1 925 44 1175 53 1 0 1 1 1000 48 1350 56 0 0 1 1 1375 44 1800 50 1 0 1 1 1375 44 1800 50
0 1 0 0 950 42 1225
51 1 1 0 0 1050 46 1375 55
0
1 0 0 1450 42 1850 48 1 1 0 0 1450 42
1850 48
0 1 0 1 1000 40 1275 49 1 1 0 1 1100 44 1400 54 0 1 0 1 1475 40 1900 47
1 1 0 1 1475 40
1900 47
0 1 1 0 1025 39 1325 47 1 1 1 0 1150 42 1450 52 0 1 1 0 1525 39 1950 46 1 1 1 0 1525 39 1950 46
0 1 1 1 1050 38 1375 45 1 1 1 1 1200 41 1500 51 0
1 1 1 1575 38 2000 45 1 1 1 1 1575 38
2000 45
1. Switch (1) selects blower program in conjunction with motor horsepower. 0 = 2 or 4 Ton, 1 = 3 or 5 Ton.
2. Recommended CFM’s (Factory settings) and temperature rises are highlighted in bold. Use of any other setting may result in nuisance trips.
3. Temperature rises in tables are approximate. Actual temperature rises may vary.