Installation Manual

18
to run through the blower off delay of approximately 150
seconds.
8. If the unit fails to prove flame after fifteen ignition
attempts, it will go into a soft lockout. The unit will re-
attempt the start-up procedure every hour until the
thermostat is satisfied or 24 VAC power is removed from
the unit for a minimum period of 5 seconds. NOTE: See
Troubleshooting section (page 21) for a complete list of
heating operation fault codes.
BlowerMode
1. On a call for fan operation, the thermostat applies 24
VAC directly to the blower contactor.
2. The circulating blower is energized immediately.
UNIT MAINTENANCE
ELECTRICAL SHOCK, FIRE OR EXPLOSION
HAZARD
Failuretofollowsafetywarningsexactlycould
resultinseriousinjuryorpropertydamage.
Improper servicing could result in dangerous
operation, serious injury, death or property
damage.
• Before servicing, disconnect all electrical
powertofurnace.
• Whenservicingcontrols,labelallwiresprior
todisconnecting.Reconnectwirescorrectly.
• Verifyproperoperationafterservicing.”
WARNING:
RISQUEDECHOCÉLECTRIQUE,D’INCENDIE
OUD’EXPLOSION
Le non-respect des avertissements de sécurité
pourrait entraîner
unfonctionnementdangereux
del’appareil,
desblessuresgraves,lamortou
des dommages matériels.
Un entretein incorrect pourrait entraîner un
fonctionnementdangereuxdel’appareil,des
blessuresgraves,lamortoudesdommages
matériels
• Couper toute alimentation électrique au
générateurd’airchaudavantdeprodéder
auxtravauxd’entretein.
• Aumomentdel’entretiendescommandes,
étiqueteztousleslsavantdelesdébrancher.
S’assurerdelesraccordercorrectement.
S’assurer que l’appareil fonctionne
adéquatementaprésl’entretien.
AVERTISSEMENT:
NOTE: These maintenance instructions are primarily
intended to assist qualified technicians experienced in
the proper maintenance and operation of this appliance.
To achieve optimum performance from the air conditioner
and minimize equipment failure, it is recommended that
periodic maintenance be performed on this unit. The
ability to properly perform maintenance on this equipment
requires certain mechanical skills and tools. Please consult
your dealer for maintenance information and availability
of maintenance contracts.
Routine Maintenance
Please consult your dealer for maintenance information
and availability of maintenance contracts.At a minimum,
routinemaintenanceshouldincludethefollowingitems:
CAUTION:
Usecarewhenremovingpartsfromthisunit.
Personal injury can result from sharp metal
edgespresentinallequipmentofsheetmetal
construction.
Air Filters
WARNING:
Neveroperatetheunitwithoutltersinplace.
Dust and lint in the return air can build up
on internal components, resulting in loss of
efciency,equipmentdamage,andpossiblere.
It is recommended that the air filters be inspected and
cleaned or replaced every three to four weeks using filters
of like size and kind. Table 1 (page 8) lists the factory
installed filter sizes and quantities for each unit.
IMPORTANTNOTE:R6GPunitsareequippedwith2”
pleateddisposablelters.Filterrackisadjustablefor
1”permanenttypelters.DONOTuse1”disposable
lters.
Blower Compartment
Build up of dirt and lint on the blower and motor can create
excessive loads on the motor resulting in higher than
normal operating temperatures and possible shortened
service life. It is recommended that the blower compartment
be cleaned monthly during heating and cooling seasons
to remove any dirt and lint that may have accumulated in
the compartment or on the blower and motor. Inspect the
blower drive belt for cracks, excessive wear and proper
tension after cleaning the compartment.
Condensate Drain & Outdoor Coil
Inspect the condensate drain and outdoor coil at the
beginning of each cooling season. Remove any debris.
Clean the outdoor coil and hail guard louvers (optional)
as necessary using a mild detergent and water. Rinse
thoroughly with water.