Table5.R6GP-072C-100CSeries-DownowConguration
R6GP-072(C/D)-100C
FactoryStandard:1HpDown-owPerformanceChart ‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Tur n
Open
1
Tur n
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
2946 2793
RPM 741 715
kW
0.85
0.77
0.2
CFM
2867 2728
2588
RPM 771 745
719
kW
0.85 0.78
0.72
0.3
CFM
2975 2828
2680 2528 2375
RPM 824 800
775 749 722
kW
0.98
0.88
0.79 0.72 0.65
0.4
CFM
2763
2608 2453 2293 2110
RPM 828
804 780 746 726
kW
0.95
0.84 0.72 0.63 0.57
0.5
CFM
2727 2582 2381 2180 1982
RPM
854 831 808 784 750
kW
0.95 0.86 0.75 0.65 0.56
0.6
CFM
2680 2488 2295 2105
1860
RPM
880 858 835 801
786
kW
0.97 0.86 0.76 0.63
0.54
0.7
CFM
2582 2399 2177
1955
RPM
908 884 862
839
kW
0.98 0.86 0.76
0.66
0.8
CFM
2528 2301 2074
1913
RPM
936 912 888
866
kW
0.97 0.86 0.76
0.68
0.9
CFM
2417 2220 2111
RPM
960 940 908
kW
1.02 0.85 0.79
1.0
CFM
2105 1854
RPM 964 944
kW
0.88 0.77
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Valuesincludeslossesfor:UnitCasing,2”Disposable(Pleated)Filters&DryEvaporatorCoil
Foroperationat208V:Deductapproximately0.5%fromCfm