Installation Manual

30
R6GP-072(C/D)-100C
FactoryStandard:1HpHorizontalPerformanceChart ‡ Indicates Factory Sheave Setting for Pre-configured Units
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Tur n
Open
1
Tur n
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3 Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
2999 2848
RPM 740 717
kW
0.86
0.76
0.2
CFM
2955 2785
2615
RPM 764 742
720
kW
0.88 0.79
0.69
0.3
CFM
2881
2738 2558 2377
RPM 792
766 745 723
kW
0.92
0.81 0.72 0.64
0.4
CFM
2812
2663 2514 2289 2085
RPM 821
795 769 745 727
kW
0.96
0.85 0.74 0.68 0.56
0.5
CFM
2729
2590 2426 2261
1995 1802
RPM 850
826 799 772
746 730
kW
0.97
0.85 0.77 0.68
0.60 0.46
0.6
CFM
2626 2462 2298 2026
1957
RPM
877 853 829 800
775
kW
0.99 0.87 0.76 0.64
0.58
0.7
CFM
2563 2349 2165
2018
RPM
903 879 855
833
kW
1.00 0.87 0.77
0.68
0.8
CFM
2545 2353 2100
1862
RPM
931 907 833
858
kW
1.02 0.91 0.78
0.68
0.9
CFM
2414 2306 2046
RPM
959 936 912
kW
1.04 0.92 0.79
1.0
CFM
2174 2013
RPM 964 941
kW
0.90 0.81
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Valuesincludeslossesfor:UnitCasing,2”Disposable(Pleated)Filters&DryEvaporatorCoil
Foroperationat208V:Deductapproximately0.5%fromCfm
Table6.R6GP-072C-100CSeries-HorizontalConguration