Installation Manual

31
Table7.R6GP-072C-166CSeries-DownowConguration
R6GP-072(C/D)-166C
FactoryStandard:1HpDownowPerformanceChart ‡ Indicates Factory Sheave Setting
External
Unit
Static
(in-Wg)
Operating
@ 230 or
460 Volts
Adjustable Motor Sheave Setting
Fully
Closed
1/2
Tur n
Open
1
Tur n
Open
1.5
Turns
Open
2
Turns
Open
2.5
Turns
Open
3
Turns
Open
3.5
Turns
Open
4
Turns
Open
4.5
Turns
Open
5
Turns
Open ‡
5.5
Turns
Open
6
Turns
Open
0.1
CFM
3025 2872
RPM 721 719
kW
0.88
0.80
0.2
CFM
2989 2832
2674
RPM 775 749
722
kW
0.92
0.83
0.74
0.3
CFM
2936 2788
2613 2437
RPM 802 776
751 725
kW
0.94 0.85
0.76 0.68
0.4
CFM
2879
2708 2537 2335 2132
RPM 831
804 777 753 728
kW
0.96
0.87 0.79 0.68 0.57
0.5
CFM
2826
2647 2437 2227
2016
RPM 857
834 808 782
756
kW
0.99
0.87 0.78 0.68
0.59
0.6
CFM
2769
2544 2318 2107
1895
RPM 881
860 838 811
784
kW
1.04
0.90 0.77 0.67
0.57
0.7
CFM
2625 2395 2220
2044
RPM
909 887 864
840
kW
1.01 0.86 0.78
0.70
0.8
CFM
2525 2323 2120
1920
RPM
937 915 892
868
kW
1.01 0.89 0.77
0.68
0.9
CFM
2449 2216 2004
RPM
964 941 919
kW
1.01 0.88 0.79
1.0
CFM
2160
1928
RPM
971
946
kW
0.92
0.81
1.1
CFM
RPM
kW
1.2
CFM
RPM
kW
Valuesincludeslossesfor:UnitCasing,2”Disposable(Pleated)Filters&DryEvaporatorCoil
Foroperationat208V:Deductapproximately0.5%fromCfm