Installation Manual Owner manual
I-RDF, PN148384R5, Page 5
4.2 Dimensions
FIGURE 1 - Dimensions (inches and mm)
Dimensions (inches)
Model Sizes A B C D E F G H J K L M
1-20-3, 1-40-3,
1-50-3, 1-65-3
88 37-1/8 44-3/16 84-13/16 45-1/2 24-1/2 10-1/2 5-7/16 14-9/32 15-5/8 21-29/32 19-1/8
2-80-3, 2-120-3 88 48-11/16 68-1/4 84-13/16 69-1/2 52 16-1/4 5-5/16 10-15/16 15-1/2 27-9/32 27-7/32
3-180-3, 3-260-3 135-3/4 61-5/8 82-9/16 132-9/16 83-1/8 64-9/16 19-1/16 5-5/32 13-13/32 21-5/8 37 37-3/32
Model Sizes N P Q R S T U V W X Y Z
1-20-3, 1-40-3,
1-50-3, 1-65-3
7-11/16 14-5/8 12-5/8 31-1/8 31-1/8 21-3/4 18-3/4 7-3/4 5-1/4 13-1/8 8-9/16 42-7/32
2-80-3, 2-120-3 16-5/16 24-21/32 11-7/32 55-3/16 42-5/8 27-1/4 27-1/4 16-5/32 6-11/32 15-3/32 8-3/4 48-15/16
3-180-3, 3-260-3 14-9/16 31-9/16 7-7/16 67-1/8 55-9/16 36-3/4 36-3/4 14-7/16 4 20-7/8 8-11/16 56
Dimensions (mm)
Model Sizes A B C D E F G H J K L M
1-20-3, 1-40-3,
1-50-3, 1-65-3
2235 943 1122 2154 1156 622 267 138 363 397 556 486
2-80-3, 2-120-3 2235 1237 1734 2154 1765 1321 413 135 278 394 691 691
3-180-3, 3-260-3 3448 1565 2097 3367 2111 1640 484 131 341 549 940 942
Model Sizes N P Q R S T U V W X Y Z
1-20-3, 1-40-3,
1-50-3, 1-65-3
195 371 321 791 791 552 476 197 133 333 217 1072
2-80-3, 2-120-3 414 626 285 1402 1083 692 692 410 161 383 222 1243
3-180-3, 3-260-3 370 802 189 1705 1411 933 933 367 102 530 221 1422
* RDF-2 and RDF-3 sys-
tems have double hinged
doors as illustrated. Control
compartment on RDF-1 has
a single hinged door.
** Conguration is for
RDF-2 and RDF-3. The
supply connection on the
RDF-1 systems is above the
control wiring connection.
5.0 Mounting
Mounting the system is the responsibility of the installer. Verify that the supporting
structure has sufcient load-carrying capacity to support the weight.
Depending on the building and its use, determine whether or not additional measures
should be taken to reduce the effect of blower vibration and/or noise.
When selecting a location for an outdoor installation, position the unit so that the air
inlet will NOT be facing into the prevailing wind. A minimum of 14" (356mm) clearance
is required from the bottom of the air inlet hood to the mounting surface.
Prior to installation, be sure that the method of support is in agreement with all local
building codes. For both indoor and outdoor installations, check for service platform
requirements. If an outdoor system is being installed with bottom discharge and/or
return air, a full perimeter roof curb is recommended.