Installation Manual

FIGURE 6A - With 120 VAC DIRECT SPARK IGNITION (DSI) SINGLE-STAGE CONTROLS
Electrical supply: 120 VAC - 60 Hz - 1 Phase.
Maximum total heater current draw: 0.14 Amps.
Total heater power consumed: 16.8 VA (16.8W).
3-wire eld service required.
Field wiring having a minimum temperature rating of at least 302°F (150°C) shall be used and supply circuit
wiring shall have a minimum size of 16 AWG (1.0mm2).
FIGURE 6B - With 24 VAC DIRECT SPARK IGNITION (DSI) SINGLE-STAGE CONTROLS
Electrical supply: 24 VAC - 60 Hz or 50 Hz - 1 Phase.
Maximum total heater current draw: 0.66 Amps.
Total heater power consumed: 15.9 VA (15.9W).
2-wire eld service required.
Field wiring having a minimum temperature rating of at least 302°F (150°C) shall be used and supply circuit
wiring shall have a minimum size of 16 AWG (1.0mm2).
GND
(-)
(+120)
GGS
BK
BK
GGS
VR*
SW*
MV*
W
W
120 VAC DSI HEATER ELECTRICAL SUPPLY AND THERMOSTAT WIRING*
LEGEND
(+120) = 120 VAC Supply Voltage
(-
(-) = Supply Neutral
GND = Earth Ground
MV* = Mechanical Ventilation*
VR* = Ventilation Relay*
SW* = Ventilation Interlock Switch*
(normally opened)
GGS = Green Ground Screw
(inside control box)
W = White Wire
– Neutral
BK = Black Wire
– 120 VAC call for heat
Thermostat
Heater 1 Heater 2
GND
(+24)
GGS
BL
BL
GGS
VR*
SW*
MV*
24 VAC DSI SINGLE-STAGE HEATER ELECTRICAL SUPPLY AND THERMOSTAT WIRING*
LEGEND
(+24) = 24 VAC Supply Voltage
GND = Earth Ground
MV* = Mechanical Ventilation*
VR* = Ventilation Relay*
SW* = Ventilation Interlock Switch*
(normally opened)
GGS = Green Ground Screw
(inside control box)
BL = Blue Wire – 24 VAC call for heat
Thermostat
Heater 1 Heater 2
7.2 Electrical
Requirements
by Voltage and
Control Types
More specic electrical requirements may vary depending on whether the unit is sin-
gle-stage (115V), single-stage (24V), or two-stage (24V). Select the information that
applies to the unit being installed.
NOTES common to FIGURES 6A, 6B, and 6C (page 12):
* Mechanical ventilation interlock is required when all combustion air is provided
by a mechanical air supply system.
#10 ring terminal is required for ground service conductor (by others) to attach to
green ground screw on heater.
The heater control is extremely polarity sensitive and the heater will cycle on
and off erratically if the electrical supply is not wired correctly. Have a qualied
electrician check that the electrical supply circuit is properly grounded and that the
electrical supply polarity is correct.
All components and wiring illustrated are eld-supplied.
Form I-RIH, P/N 131793R8, Page 11