Installation Manual

24 VAC – 60 or 50 Hz – 1 Phase
Heater Maximum Current Draw = 0.66 Amps.
Total Heater Power Consumed = 15.9 VA
FIGURE 7B - 24 VAC SINGLE-STAGE
DIRECT SPARK IGNITION ELECTRICAL
CONNECTION DIAGRAM
G(3)
O
O
Y
(+24)
BL
GND
Green Ground
Screw (GGS)
G(1)
G(1)
G(2)
R(1)
R(2)
R(1)
G(2)
BL
Y
Wire Colors
BK = Black
G = Green
O = Orange
R = Red
W = White
Y =Yellow
field wiring
Combination
Gas Valve (CGV)
Ignition
Control
(IDC)
Flame
Sensor
(FS)
Spark
Electrode
(SE)
NOTES:
Control is polarity sensitive
Installer to provide and install #10 ring terminal required for ground service conductor to attach to green ground screw in
heater control box.
See Paragraphs 7.1 and 7.2 for detailed information on electrical supply and thermostatic control.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a
temperature rating of at least 302°F (150°C) and a minimum size of 16 AWG (1.0mm
2
)
24 VAC – 60 or 50 Hz – 1 Phase
Heater Maximum Current Draw = 0.96 Amps.
Total Heater Power Consumed = 23.1 VA
FIGURE 7C - 24 VAC 2-STAGE DIRECT
SPARK IGNITION ELECTRICAL
CONNECTION DIAGRAM
Wire Colors
BK = Black
G = Green
O = Orange
R = Red
W = White
Y =Yellow
field wiring
Combination
Gas Valve (CGV)
Flame
Sensor
(FS)
Flame
Sensor
(FS)
Spark
Electrode
(SE)
Ignition
Control
(IDC)
High Heat
Valve (HHV)
NOTES:
Control is polarity sensitive
Installer to provide and install #10 ring terminals required for ground service conductor and for common/neutral service
conductor to attach to green ground screw in heater control box.
See Paragraphs 7.1 and 7.2 for detailed information on electrical supply and thermostatic control.
If any of the original wire as supplied with the appliance must be replaced, it must be replaced with wiring material having a
temperature rating of at least 302°F (150°C) and a minimum size of 16 AWG (1.0mm2).