Heater Suspension
⚠ WARNING ⚠
Before suspending the heater, check the supporting structure to be used to verify that it has
sufficient load-carrying capacity to support the weight (refer to Weights section) of the unit.
The heater must be level for proper operation. DO NOT place or add additional weight to a
suspended heater.
⚠ CAUTION ⚠
Before lifting the heater, verify that any screws used for holding shipping brackets were re-
installed in the cabinet.
Before lifting heater model UBZ or UDZ, any unused suspension points on the control side of
the heater MUST be plugged.
When the heater is lifted for suspension, support the bottom of the heater with plywood or other
appropriately placed material. If the bottom is not supported, damage could occur.
The heater is designed to be suspended using either two- or four-point suspension. A 3/8-16 threaded nut retainer
is located at each suspension point. The heater may be suspended using either 3/8-inch threaded rods or a hanger
kit option package.
On heater models UBX and UDX, shipped-separate option packages—that should be installed before the heater
is suspended—include vertical louvers, high-elevation kit, multiple heater control, sensor for DDC control, and/
or stepdown transformer. Installation instructions for these option packages are included in the option package.
In the literature bag shipped with the heater, there are three capscrews (PN 203311) and sealing washers (PN
61658). On UBZ and UDZ models, these capscrews and washers must be used to seal any unused holes in the
top of the heater (control side) after attaching the hanging hardware (see Figure 5).
Figure 5. Plugging Unused Suspension Points (Models UBZ and UDZ Only)
PLUG ANY UNUSED SUSPENSION POINT(S)