Install Instructions
Table Of Contents
- UNIT HEATER INSTALLATION/OPERATION/MAINTENANCE: (MODEL UBX: STANDARD POWER VENT BLOWER TYPE, MODEL UBZ: SEPARATED-COMBUSTION BLOWER TYPE, MODEL UDX: STANDARD POWER VENT FAN TYPE, MODEL UDZ: SEPARATED-COMBUSTION FAN TYPE)
- TABLE OF CONTENTS
- GENERAL INFORMATION
- INSTALLATION
- CONTROLS
- OPERATION
- ADJUSTMENTS
- MAINTENANCE
- Service Checklist
- Maintenance Procedures
- Burner Maintenance
- Burner Orifice Maintenance
- Heat Exchanger Maintenance
- Ignition System Maintenance
- Maintenance of Fan Motor, Fan Blades, and Fan Guard
- Venter Motor and Wheel Assembly Maintenance
- Operating Gas Valve Maintenance
- Pressure Switch Maintenance
- High Temperature Limit Control Maintenance
- Flame Rollout Switch Maintenance (Model UDZ Unit Sizes 030–125 Only)
- Interlock Door Switch Maintenance (Models UBZ and UDZ Only)
- Transformer Maintenance
- Disconnect Switch Replacement (Models UBZ and UDZ Only)
- Vent or Vent/Combustion Air System Maintenance
- TROUBLESHOOTING
- INSTALLATION RECORD (TO BE COMPLETED BY INSTALLER)
- FIGURES
- Figure 1. Heater Throw Patterns (Refer to Table 2 and Table 3)
- Figure 2. Dimensions—Models UBX and UBZ (Refer to Table 4)
- Figure 3. Dimensions—Models UDX and UDZ (Refer to Table 5)
- Figure 4. Confined Space Combustion Air Openings (Refer to Table 8)
- Figure 5. Plugging Unused Suspension Points (Models UBZ and UDZ Only)
- Figure 6. Option CK8 or CK10 Hanger Kit
- Figure 7. Option CK22 Hanger Kit
- Figure 8. Heater Suspension Using Field-Supplied Threaded Rods
- Figure 9. Gas Connections
- Figure 10. Supply Wiring Entrance and Control Connection Terminal Strip
- Figure 11. Circuit Board (DSI Control Module)
- Figure 12. Component Locations (Typical)
- Figure 13. Gas Valve ON/OFF Control
- Figure 14. Pressure Switch
- Figure 15. Gas Valves
- Figure 16. Typical Burner Assembly
- Figure 17. Ignitor Spark Gap
- Figure 18. Fan Blade Positioning and Spacing
- Figure 19. Venter Motor and Wheel Assembly
- Figure 20. Replaceable Components
- Figure 21. DSI Control Module Troubleshooting Flowchart
- TABLES
- Table 1. Related Technical Manuals Available from Factory Distributor
- Table 2. Heater Throw Distances with Standard Horizontal Louvers at Mounting Heights of 5 to 18 Feet
- Table 3. Heater Throw Distances with Standard Horizontal Louvers at Mounting Heights of 1.5 to 5.5 Meters
- Table 4. Dimensions—Models UBX and UBZ
- Table 5. Dimensions—Models UDX and UDZ
- Table 6. Clearances to Combustibles
- Table 7. Unit Weights
- Table 8. Determining Confined Space Combustion Air Requirements
- Table 9. Technical Data for UBX and UBZ Models (Unit Sizes 030–125)
- Table 10. Technical Data for UBX and UBZ Models (Unit Sizes 150–400)
- Table 11. Technical Data for UDX and UDZ Models (Unit Sizes 030–125)
- Table 12. Technical Data for UDX and UDZ Models (Unit Sizes 150–400)
- Table 13. Field-Installed Options
- Table 14. Gas Supply Line Sizes
- Table 15. Gas Connection Sizes
- Table 16. Pressure Switch Settings
- Table 17. Circuit Board (DSI Control Module) Display Codes
- Table 18. Operating Sequence (Normal Heat Cycle)
- Table 19. Operating Sequence (Abnormal Heat Cycle)
- Table 20. Fault Modes
- Table 21. Required Manifold (Outlet) Gas Pressure
- Table 22. Inputs and Capacities by Elevation in US
- Table 23. Inputs and Capacities by Elevation in Canada
- Table 24. Fan Blade Spacing
- Table 25. General Troubleshooting
24
I-UBX-UBZ-UDX-UDZ (04-21) 1034344-0
CONTROLS—CONTINUED
Pressure Switch—Continued
• If a restriction or excessive flue length/turns cause the sensing pressure to be outside the pressure switch setpoint,
the switch will function to shut off the main burner. The main burner will remain off until the system has cooled
and/or the flue system resistance is reduced.
• Pressure switch settings are listed in Table 16.
Table 16. Pressure Switch Settings
UBX and UDX Models
Unit Size
Negative Pressure (IN WC)
Label Color
Startup Cold Equilibrium Hot Setpoint OFF Setpoint ON
030 1.20 0.90 0.30 0.45 Orange
045 (UBX) 1.00 0.80 0.25 0.40 Red
045 (UDX) 1.00 0.80 0.40 0.55 Green
060 0.90 0.80 0.35 0.50 Purple
075 0.80 0.70 0.45 0.60 Pink
100 0.90 0.70 0.50 0.65 Orange
125 1.40 1.00 0.70 0.85 Wine
150 0.70 0.60 0.35 0.50 Purple
175 0.80 0.70 0.40 0.55 Green
200, 225 2.30 1.60 1.10 1.30 Blue
250 2.70 1.80 1.10 1.30 Blue
300 2.50 1.90 1.10 1.30 Blue
350, 400 2.10 1.60 1.10 1.30 Blue
UBZ and UDZ Models
Unit Size
Differential Pressure (IN WC)
Label Color
Startup Cold Equilibrium Hot Setpoint OFF Setpoint ON
030 (UBZ) 1.20 0.90 0.30 0.45 Orange
030 (UDZ) 1.20 0.90 0.40 0.55 Green
045 (UBZ) 1.00 0.80 0.35 0.50 Purple
045 (UDZ) 1.00 0.80 0.40 0.55 Green
060 1.20 0.80 0.35 0.50 Purple
075 1.00 0.80 0.45 0.60 Pink
100 0.90 0.80 0.50 0.65 Orange
125 (UBZ) 1.30 1.00 0.70 0.85 Wine
125 (UDZ) 1.30 1.00 0.80 0.95 Gray
150 0.70 0.55 0.35 0.50 Purple
175 0.75 0.65 0.40 0.55 Green
200 2.60 1.80 1.10 1.30 Blue
225 2.50 1.60 1.10 1.30 Blue
250 2.60 1.80 1.10 1.30 Blue
300 (UBZ) 2.70 1.85 1.10 1.30 Blue
300 (UDZ) 2.70 1.85 1.30 1.50 White
350 2.25 1.80 1.50 1.70 Yellow
400 2.10 1.60 1.30 1.50 White