Replacement Parts

8
P-UBX-UBZ-UDX-UDZ (05-21) 1034346-0
ELECTRICAL COMPONENTS—CONTINUED
—Continued
Table 5. Stepdown Transformer Kit (Option CG1, CG2, or CG4) Components
Component Model
Option*
Unit Size
030 045 060, 075 100 125
150, 175,
200
225, 250
300, 350,
400
PN
Common Parts—Continued
Cable clamp, 1/2
(Heyco #3328)
UBX,
UBZ
All
16227
UDX,
UDZ
16227
Screw, sheet metal,
#10 × 1/2
(quantity = 3)
UBX,
UBZ
11813
UDX,
UDZ
11813
Wire connector,
73B (Ideal #3-0253,
quantity = 10)
UBX,
UBZ
16354
UDX,
UDZ
16354
*Option CG1 is for 208V supply 120V, option CG2 is for 230V supply 120V, and option CG4 is for 460V supply 120V.
Table 6. Fan Blade/Motor Spacing and Fan Guard Type
Unit Size
Wire Fan Guard Type
Setscrew Torque
(inch-pounds ±10)
Standard Guard
(0.5-Inch (13-mm) Spacing)
Option AZ8 Guard
(0.334-Inch (8.5-mm) Spacing)
Dimension A (Inches (mm))*
030 1 (25)
80
045 9/16 (14) 1-1/16 (27)
060 1-1/2 (38) 1-3/4 (44)
075 2-1/8 (54) 1-1/2 (38)
100 2-3/8 (60)
120
125 2-5/16 (59) 2-1/8 (54)
150 2-3/8 (60)
130
175 2-1/8 (54)
200 1-5/8 (41)
225, 250, 300 2 (51)
350 1-7/8 (48)
400 1-3/8 (35)
*See Figure 3.
Figure 3. Fan Spacing
A
Fan
Blade
Motor
Setscrew
A
Motor
Fan
Blade
Setscrew
UNIT SIZES 030–250
UNIT SIZES 300–400
FAN AND MOTOR COMPONENTS