UDZ Venting Instructions

Table Of Contents
10
CP-UBZ-UDZ-VENT (02-21) 1034632-0
INSTALLATION—CONTINUED
Vent Terminal Options—Continued
Vertical Vent Terminal (Option CC2) Installation—Continued
Shaded area represents
required continuous
(no joints) section of
vent pipe. Section of
pipe may extend higher.
Vent Pipe
Rear
View
Side View
Figure 7. Option CC2 Installation
2. Install vent pipe and combustion air pipe runs:
a. Connect piping to heater in accordance with specifications listed in Venting and Combustion Air Requirements
section and subsections.
b. Seal all joints in accordance with specifications listed in Joint Connection and Sealing Requirements section.
Due to high temperature considerations, do not enclose exhaust pipe or place pipe closer than 6 inches (152
mm) to combustible material.
c. Extend piping runs close to roof at location selected in step 1 and support piping in accordance with specifications
listed in Vent System Support Requirements section.
NOTE: The vent pipe will extend through the roof after the concentric adapter box is installed. The
indoor combustion air pipe will end at the box.
3. Cut hole through outside wall for combustion air pipe.
a. Ensure that location and orientation of concentric adapter box are correct and mark and cut hole.
b. Ensure that hole accommodates 6-inch (152 mm) combustion air pipe for unit sizes 030–125 or 8-inch (203-
mm) combustion air pipe for unit sizes 150–400. Thimble may or may not be required depending on building
construction and/or local codes. Larger diameter combustion air pipe serves as clearance for vent pipe on
non-combustible construction.