UDZ Installation Manual

Table Of Contents
18
UBX-UBZ-UDX-UDZ-IOM (03-22) 1034344-C
Figure 6. Option CK10 Hanger Kit
Suspension of Heater Using Option CK22 Hanger Kit
The ceiling suspension kit (option CK22, see Figure 7) allows the heater to be installed 1 inch from the ceiling without
hanger rods. The ceiling suspension kit is used only on unit sizes 030–125 for UDX and UDZ models. Refer to the
installation instructions provided with the kit.
INSTALLATION—CONTINUED
Heater Suspension—Continued
Suspension of Heater with Downturn Nozzle
Downturn nozzle kits (option CD2, CD3, CD4, or CD5) require four-point suspension. Follow the instructions provided
with the kit for downturn nozzle installation.
Suspension of Heater Using CK10 Hanger Kit
Option CK10 (four-point suspension) is for suspending the heater using swivel connectors connected to 1-inch pipe.
Attach the swivel connectors at the 3/8-16 threaded nut retainers. Ensure that the swivel connectors are locked to
the heater as shown in Figure 6.
Figure 7. Option CK22 Hanger Kit