Acoustical Considerations
Refer to sound level data listed in Technical Data section when determining unit location based on acoustical
considerations.
Technical Data
Table 9, Table 10, Table 11, and Table 12 list unit technical data.
GENERAL INFORMATION—CONTINUED
Combustion Air Requirements—Continued
Table 8. Determining Confined Space Combustion Air Requirements
Letter*
Air Source Required Opening Size
Calculate Combustion Air
Requirements
A Air inside building
1 square inch free area per 1000 BTUh
Add total BTUh of all appliances in
confined space and divide by figures
at left for square inch free area size of
each (top and bottom) opening
Never <100 square inches free area for each opening
B Outside air through duct 1 square inch free area per 2000 BTUh
C Direct outside air 1 square inch free area per 4000 BTUh
*See Figure 4.
Table 9. Technical Data for UBX and UBZ Models (Unit Sizes 030–125)
Parameter
Unit Size
030 045 060 075 100 125
Input heating capacity (BTUh) 30,000 45,000 60,000 75,000 105,000 120,000
Input heating capacity (kW) 8.8 13.2 17.6 22.0 30.8 35.2
Thermal efficiency (%) 82 82 83
Output heating capacity (BTUh)
1
24,600 36,900 49,200 61,500 87,150 99,600
Output heating capacity (kW)
1
7.2 10.8 14.4 18.0 25.6 29.2
Gas connection, natural (inches)
2
1/2 1/2 1/2
Gas connection, propane (inches)
2
1/2 1/2 1/2
Vent connection diameter (inches)
3
4 4 4
Combustion air inlet diameter, UBZ models (inches)
3
4 4 4
Control, 24V (amps) 1.0 1.0 1.0
Full load amps, 115V, UBX models (amps) 3.7 7.1 13.0
Full load amps, 115V, UBZ models (amps) 3.7 7.1 7.3 13.2
Maximum overcurrent protection, 115V (amps)
4
15 15 30
Discharge air temperature rise, minimum/maximum (°F) 45/75 45/75 45/75
Minimum air volume (cfm) 304 456 607 759 1076 1230
Minimum air volume (meters/minute)
3
8.6 12.9 17.2 21.5 30.5 34.8
Maximum air volume (cfm) 506 759 1012 1265 1793 2049
Maximum air volume (meters/minute)
3
14.3 21.5 28.7 35.8 50.8 58.0
Discharge air opening area (feet)
2
0.96 1.25 2.01
Discharge air opening area (meters)
2
0.09 0.12 0.19
Minimum output velocity (fpm) 316 475 486 607 535 612
Minimum output velocity (meters/minute) 96 143 143 179 160 183
Maximum output velocity (fpm) 527 791 810 1012 892 1020
Maximum output velocity (meters/minute) 159 239 239 299 267 305
Standard blower motor size (horsepower) 1/6 1/3 3/4
Blower fan size (inches) 9 × 6 9 × 6 10 × 10
Sound level @ 15 feet (dBa) 40 40 49 54 55
1
CSA ratings for elevations up to 2,000 feet.
2
Size shown is for gas connection to a single-stage gas valve—not supply line size.
3
Smaller and/or larger vent and combustion air pipe diameters may be permissible. Refer to appropriate venting instructions listed in Table 1.
4
MOCP = 2.25 × (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.