Table 10. Technical Data for UBX and UBZ Models (Unit Sizes 150–400)
Parameter
Unit Size
150 175 200 225 250 300 350 400
Input heating capacity (BTUh) 150,000 175,000 200,000 225,000 250,000 300,000 350,000 400,000
Input heating capacity (kW) 43.9 51.2 58.6 65.9 73.2 87.8 102.5 117.1
Thermal efficiency (%) 83 83 83 83 82
Output heating capacity (BTUh)
1
124,500 145,250 166,000 186,750 207,500 249,000 290,500 328,000
Output heating capacity (kW)
1
36.4 42.5 48.6 54.7 60.8 72.9 85.1 96.0
Gas connection, natural (inches)
2
1/2 1/2 3/4 3/4 3/4
Gas connection, propane (inches)
2
1/2 1/2 3/4 3/4 3/4
Vent connection diameter (inches)
3
5 5 5 6 6
Combustion air inlet diameter, UBZ models (inches)
3
6 6 6 6
Control amps, 24V (amps) 1.0 1.0 1.0 1.0
Full load amps, 115V, UBX models (amps) 5.9 9.6 10.5 12.7 12.7 17.7 27.3
Full load amps, 115V, UBZ models (amps) 5.9 6.3 10.5 12.7 12.7 17.7 27.3
Maximum overcurrent protection, 115V, UBX models (amps)
4
15 20 25 30 30 40 60
Maximum overcurrent protection, 115V, UBZ models (amps)
4
15 25 30 30 40 60
Discharge air temperature rise, minimum/maximum (°F) 45/75 45/75 45/75 45/75 50/80
Minimum air volume (cfm) 1537 1793 2049 2306 2562 3074 3586 4100
Minimum air volume (meters/minute)
3
43.5 50.8 58.0 65.3 72.5 87.0 101.5 116.1
Maximum air volume (cfm) 2562 2989 3416 3843 4270 5123 5977 6185
Maximum air volume (meters/minute)
3
72.5 84.6 96.7 108.8 120.9 145.1 169.2 175.1
Discharge air opening area (feet)
2
2.56 2.56 3.51 3.51 4.79 4.79
Discharge air opening area (meters)
2
0.24 0.24 0.33 0.33 0.45 0.45
Minimum output velocity (fpm) 600 700 800 657 730 642 749 856
Minimum output velocity (meters/minute) 183 213 244 200 223 196 228 261
Maximum output velocity (fpm) 1001 1168 1334 1095 1217 1070 1248 1291
Maximum output velocity (meters/minute) 305 356 407 334 371 326 380 393
Standard blower motor size (horsepower) 1/4 1/2 1/2 3/4 3/4 1-1/2 2
Blower fan size (inches) 12 × 12 12 × 12 15 × 11 15 × 11 15 × 15
Sound level @ 15 feet (dBa) 51 52 53 56 56 59 61 62
1
CSA ratings for elevations up to 2,000 feet.
2
Size shown is for gas connection to a single-stage gas valve—not supply line size.
3
Smaller and/or larger vent and combustion air pipe diameters may be permissible. Refer to appropriate venting instructions listed in Table 1.
4
MOCP = 2.25 × (largest motor FLA) + smallest motor FLA. Answer is rounded to the next lower standard circuit breaker size.