UDZ Venting Instructions

Table Of Contents
9
CP-UBZ-UDZ-VENT (02-21) 1034632-0
Table 6. Vertical Vent Terminal/Combustion Air Package (Option CC2) Components
Unit Size
Description Qty030–125 150–400
PN
205895 205896 Kit package 1
205884 205885 Concentric adapter box (see Figure 2, Figure 3, and Figure 4) 1
110051 110052 Exhaust vent terminal assembly (see Figure 6) 1
155635 53330 Combustion air inlet assembly (see Figure 6) 1
207232 Concentric adapter box bracket 2
53335 High-temperature silicone sealant, tube 1
EXHAUST VENT TERMINAL ASSEMBLY
COMBUSTION AIR INLET ASSEMBLY
Figure 6. Option CC2 Components
Install the vertical vent kit as follows:
⚠ DANGER ⚠
To prevent combustion products from entering the occupied space, all vent terminals must be
positioned or located away from fresh air intakes, doors, and windows. Failure to comply could
result in severe personal injury or death and/or property damage.
1. Determine vent terminal location on outside wall:
a. If more than one vertical vent terminal is being installed, minimum spacing between vent center lines is
determined by minimum outdoor design temperature (coldest outdoor condition at installation site). Refer to
Table 7 to ensure that location complies with minimum outdoor design temperature requirements.
Table 7. Minimum Spacing Between Center Lines of Vertical Vent Pipes
Minimum Outdoor Design Temperature
Minimum Spacing Between Center Lines of Vertical Vent Pipes
(Inches (mm))
31°F (0°C) 36 (914)
10 to 30°F (23 to 1°C) 60 (1524)
< 10°F (< 23°C) 84 (2134)
b. Select location away from fresh air intakes, allowing space for concentric adapter box inside. Vent terminal
must be located away from adjacent buildings as shown in Figure 7.