Operating instructions
1104UESAGBEN, page 31/31
ADDENDUM : TECHNICAL DATA
(1) Gas appliance classifi cations for approved venting methods based on CEN-report CR1749:2001
(2) There is a difference between the gas connection and the pipe size of the supply line. Always use the most suitable pipe size to
minimize the pressure drop through the gas pipes - if necessary, reduce the pipe size of the supply line at the inlet of the unit.
(3) Figure for isothermal conditions.
(4) Height from fl oor to bottom surface of heater. These are recommendations only positioning of unit heaters for proper performance
is application dependent Operation is affected by other air moving equipment in the space, obstructions to the airfl ow, draughts
and/or close proximity to doors or windows, etc… Care should taken to avoid mounting the heaters above these recommendations,
unless downturn nozzle options are used, as signifi cant stratifi cation may occur resulting in poor fl oor coverage and higher energy
losses through the roof structure.
(5) Isothermal conditions at 20°C ambient air temperature, discharge louvre zero defl ection, v = 0,5 m/s. The air throw will be infl u-
enced by the height of the building, mounting height of the unit, ambient temperature & adjustment of the louvres.
(6) Sound pressure level in dB(A) in free fi eld conditions, measured at 5 meters from the unit
(7) Sound pressure level in dB(A), measured at 5 metres from the unit with A=160m² and Q=2
(8) Measured at nominal input rate with G20 at 20°C ambient
Type UESA 035 055 083 102
Gas category II2H3+
Comb. Air & Flue, type B (1) B22p
Comb. Air & Flue, type C (1) C12, C32, C52, C62, C82
Connection collars mm 100 100 130 130
Heat input Hs kW 37,8 58,6 88,1 107,7
Heat input Hi kW 34,00 52,80 79,30 97,00
Heat output kW 34,9 54,4 82,2 101,2
Thermal Effi ciency % 102,6 103,1 103,7 104,3
Gas consumption
natural gas G20 m³/h 3,6 5,6 8,4 10,3
propane G31 kg/h 2,6 4,1 6,2 7,5
Gas pipe connection (2) 3/4”
Temperature rise (3) K 26 26 27 28
Air fl ow (3) m³/h 3900 6190 9060 10570
Nominal motor speed RPM 900 1320 900 900
maximum mounting height (4) m 3,5 3,5 4 4
Horizontal throw (5) m 25 40 34 36
Sound Power dB(A) 67 72.5 74 73
Sound Pressure (6) dB(A) 45 50.5 52 51
Sound Pressure (7) dB(A) 52 57.5 59 58
Electrical service (protection IP20) 230/240V 1N~50Hz
Total electrical rating W 628 841 990 1300
Flow of condensation products (8) l/h 2,3 3,1 6,6 7,5
Net weight kg 148 151 222 230