Instructions / Assembly

39
INSTALLATION INSTRUCTIONS
Venting
Horizontal Vent Considerations
WARNING: Moisture in the flue gas 
will condense as it leaves the vent terminal. In cold 
weather this condensate can freeze on the exterior 
wall, under the eaves, and on surrounding objects. 
Some discoloration to the exterior of the building 
is to be expected. However, improper location 
or installation can result in severe damage to the 
structure or exterior finish of the building.
–  Do not install vent terminals under any patio or 
deck.
–  Do not locate vent terminal on the side of a 
building with prevailing winter winds. This will 
help prevent water lines from freezing and 
moisture from freezing on walls and under 
eaves.
–  Do not locate vent terminal too close to 
shrubbery, since flue gases may damage them.
–  All painted surfaces should be primed to 
lessen the chance of physical damage. Painted 
surfaces will require maintenance.
–  Guard against accidental contact with people 
and pets.
INDOOR TANKLESS WATER 
HEATERS
WARNING: For multiple-unit 
installation, a minimum distance between vent 
terminations must be maintained to prevent 
recirculation of vent gases. Maintain a center-
to-center distance between each pair of vent 
terminations of 24 in. (61 cm) for a two-unit 
installation; 24 in. (61 cm) and 36 in. (91.4 cm) for 
an installation of three units; and 24 in. (61 cm), 
36 in. (91.4 cm), and 24 in. (61 cm) for an 
installation of four units. 
–  Do not terminate vent directly on brick or 
masonry surfaces. Use rust-resistant, sheet-
metal backing plate of 1 sq. ft. (30 sq. cm) 
behind the vent.
–  Caulk all cracks, seams, and joints within  
6 ft. (1.8 m) of the vent terminal.
–  Caulk around wall faceplate for weather-tight 
seal.
–  Do not extend exposed vent pipe of indoor 
water heaters outside of the building.
–  This water heater requires its own separate 
venting system. Do not connect the exhaust 
vent to an existing vent pipe or chimney. 
OUTDOOR TANKLESS WATER 
HEATERS
–  Install outdoor water heater such that air inlet 
and flue outlet are above anticipated snow level.
Rising moisture will collect under eaves.
Inside
Corner
Caulk
Caulk
Caulk
Caulk
If soft vent is too close,
block off and install new
vent at another location.
6' (1.8 m) Caulk zone or 
to edge of window etc., 
starting within 6' (1.8 m)
4' 
(1.2 m)
Rising moisture will collect under eaves.
Inside
Corner
Caulk
Caulk
Caulk
If soft vent is too close,
block off and install new
vent at another location.
6' (1.8 m) Caulk zone
or to edge of window
etc., starting within 
6' (1.8 m)
4' 
(1.2 m)
12" 
(300 mm)