Specification Sheet
Air
Performance Data
16AJL Series
12
Outdoor
Unit
16AJL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor
Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
36
RCFN-H*3624 ROLA-115E05
1 22300 [6.5] 8300 [2.4]
38500 [11.3] 16 13
900 [425] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
RCFN-H*3624+RXMD-C04 Coil Only
1 20800 [6.1] 8600 [2.5]
37200 [10.9] 14.5 12
800 [378] 0
2 27000 [7.9] 10200 [3.0] 1050 [495] 77
RCSL-H*3821 RHPL-HM3821
1 20700 [6.1] 8700 [2.5]
35800 [10.5] 16 12.5
950 [448] 0
2 25300 [7.4] 10500 [3.1] 1150 [543] 77
RCSN-H*3624 RHPN-HM3624
1 20900 [6.1] 8900 [2.6]
38500 [11.3] 16 13
725 [342] 0
2 29000 [8.5] 9500 [2.8] 1200 [566] 77
48
RCSL-H*4824
➀
RHML-HM4824
1 26900 [7.9] 12100 [3.5]
48500 [14.2] 16 13
1050 [495] 0
2 34700 [10.2] 13800 [4.0] 1400 [661] 77
1 - dehumid 0 [0.0] 0 [0.0] 0 [0]
2 - dehumid 0 [0.0] 0 [0.0] 0 [0]
RCFL-H*4821
RGFE-10?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1425 [672] 77
RGFG-09?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGFG-10?ZCM?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1050 [495] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGGE-09?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGGE-10?ZCM?
1 24000 [7.0] 12600 [3.7]
45500 [13.3] 15 11.5
1050 [495] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGJF-09?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGJF-10?ZCM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGLE-07?BRQ?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 11.5
1025 [484] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGLE-10?BRM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15.5 12
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGPE-07?BRQ?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 12
1050 [495] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGPE-10?BRM?
1 24000 [7.0] 12600 [3.7]
46000 [13.5] 15 12
1075 [507] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
RGRM-07?YBG?
1 23600 [6.9] 12600 [3.7]
45000 [13.2] 14 10.5
1050 [495] 0
2 30100 [8.8] 14900 [4.4] 1400 [661] 77
RGRM-09?ZAJ?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 14.5 11.5
1075 [507] 0
2 30600 [9.0] 14900 [4.4] 1400 [661] 77
RGRM-10?ZAJ?
1 23800 [7.0] 12600 [3.7]
45500 [13.3] 14.5 11
1025 [484] 0
2 30600 [9.0] 14900 [4.4] 1425 [672] 77
RGTM-07?RBG?
1 24700 [7.2] 12300 [3.6]
46000 [13.5] 15 11.5
1125 [531] 0
2 31600 [9.3] 14400 [4.2] 1475 [696] 77
RGTM-09?ZAJ?
1 24400 [7.1] 12400 [3.6]
46000 [13.5] 15 11.5
1100 [519] 0
2 31100 [9.1] 14900 [4.4] 1400 [661] 77
Rev.
5/8/2012
➀ Highest sales volume tested combination required by D.O.E. test procedures.
[ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling