Specification Sheet
Air
Performance Data
RARL- JEC Series
15
Outdoor
Unit
RARL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
038JEC
RCFL-H*3824
ROCA-070E03
1 18400 [5.4] 9800 [2.9]
34600 [10.1] 15 12
800 [378] 71
2 22700 [6.7] 11900 [3.5] 1000 [472] 72
ROCA-070E04
1 18400 [5.4] 9800 [2.9]
34600 [10.1] 15 12
800 [378] 71
2 22700 [6.7] 11900 [3.5] 1000 [472] 72
ROLA-070E03
1 19600 [5.7] 9400 [2.8]
35400 [10.4] 15 12
900 [425] 71
2 24200 [7.1] 11200 [3.3] 1175 [554] 72
ROLA-070E04
1 19600 [5.7] 9400 [2.8]
35400 [10.4] 15 12
900 [425] 71
2 24200 [7.1] 11200 [3.3] 1175 [554] 72
ROLA-115E05
1 19600 [5.7] 9400 [2.8]
35600 [10.4] 15 12
900 [425] 71
2 24500 [7.2] 11100 [3.3] 1200 [566] 72
RCFL-H*3824+RXMD-C06 Coil Only
1 18800 [5.5] 9400 [2.8]
34800 [10.2] 13 11.5
925 [437] 71
2 23400 [6.9] 11400 [3.3] 1125 [531] 72
RCFN-H*3624
RGFE-06?MCK?
1 20300 [5.9] 9300 [2.7]
37200 [10.9] 16 12.5
725 [342] 71
2 26100 [7.6] 11100 [3.3] 1000 [472] 72
RGFE-07?MCK?
1 20300 [5.9] 9300 [2.7]
37200 [10.9] 16 12.5
725 [342] 71
2 26200 [7.7] 11000 [3.2] 1025 [484] 72
RGFE-09?ZCM?
1 21800 [6.4] 8800 [2.6]
38000 [11.1] 16 12.5
875 [413] 71
2 27800 [8.1] 10200 [3.0] 1200 [566] 72
RGFE-10?ZCM?
1 22200 [6.5] 8600 [2.5]
38500 [11.3] 16 12.5
900 [425] 71
2 28400 [8.3] 10100 [3.0] 1225 [578] 72
RGFE-12?RCM?
1 21800 [6.4] 8800 [2.6]
38500 [11.3] 16.5 13
875 [413] 71
2 28400 [8.3] 10100 [3.0] 1225 [578] 72
RGFG-06?MCK?
1 20300 [5.9] 9300 [2.7]
37200 [10.9] 16 12.5
725 [342] 71
2 26100 [7.6] 11100 [3.3] 1000 [472] 72
RGFG-07?MCK?
1 20900 [6.1] 9100 [2.7]
37000 [10.8] 16 12.5
800 [378] 71
2 25900 [7.6] 11100 [3.3] 1000 [472] 72
RGFG-09?ZCM?
1 21800 [6.4] 8800 [2.6]
38000 [11.1] 16 12.5
875 [413] 71
2 27800 [8.1] 10200 [3.0] 1200 [566] 72
RGFG-10?ZCM?
1 22200 [6.5] 8600 [2.5]
38000 [11.1] 16 12.5
900 [425] 71
2 27800 [8.1] 10200 [3.0] 1200 [566] 72
RGFG-12?RCM?
1 21800 [6.4] 8800 [2.6]
38500 [11.3] 16.5 13
875 [413] 71
2 28400 [8.3] 10100 [3.0] 1225 [578] 72
RGGE-06?MCK?
1 20500 [6.0] 9300 [2.7]
37400 [11.0] 16 13
725 [342] 71
2 26400 [7.7] 11000 [3.2] 1025 [484] 72
RGGE-07?MCK?
1 20600 [6.0] 9200 [2.7]
37400 [11.0] 16 12.5
750 [354] 71
2 26400 [7.7] 11000 [3.2] 1025 [484] 72
RGGE-09?ZCM?
1 21800 [6.4] 8800 [2.6]
38500 [11.3] 16 13
875 [413] 71
2 28400 [8.3] 10100 [3.0] 1225 [578] 72
RGGE-10?ZCM?
1 21800 [6.4] 8800 [2.6]
38000 [11.1] 16 13
875 [413] 71
2 27800 [8.1] 10200 [3.0] 1200 [566] 72
RGGE-12?RCM?
1 21800 [6.4] 8800 [2.6]
38500 [11.3] 16.5 13
875 [413] 71
2 28300 [8.3] 10200 [3.0] 1200 [566] 72
RGJF-06?MCK?
1 20500 [6.0] 9300 [2.7]
37400 [11.0] 16 13
725 [342] 71
2 26400 [7.7] 11000 [3.2] 1025 [484] 72
RGJF-07?MCK?
1 20600 [6.0] 9200 [2.7]
37400 [11.0] 16 12.5
750 [354] 71
2 26400 [7.7] 11000 [3.2] 1025 [484] 72
Rev.
5/8/2012
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling