Specification Sheet
Air
Performance Data
RARL- JEC Series
21
Outdoor
Unit
RARL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
049JEC RCFL-H*4824
RGFE-09?ZCM?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11
1025 [484] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGFE-10?ZCM?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11
1025 [484] 72
2 28400 [8.3] 16100 [4.7] 1425 [672] 72
RGFE-12?RCM?
1 23700 [6.9] 14300 [4.2]
45000 [13.2] 15 11.5
1025 [484] 72
2 29000 [8.5] 16000 [4.7] 1450 [684] 72
RGFG-09?ZCM?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11
1025 [484] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGFG-10?ZCM?
1 23800 [7.0] 14200 [4.2]
44500 [13.0] 15 11
1050 [495] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGFG-12?RCM?
1 23700 [6.9] 14300 [4.2]
45000 [13.2] 15 11.5
1025 [484] 72
2 29000 [8.5] 16000 [4.7] 1450 [684] 72
RGGE-09?ZCM?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11.5
1025 [484] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGGE-10?ZCM?
1 23800 [7.0] 14200 [4.2]
44500 [13.0] 15 11.5
1050 [495] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGGE-12?RCM?
1 25500 [7.5] 13500 [4.0]
45500 [13.3] 15 11.5
1200 [566] 72
2 30400 [8.9] 15100 [4.4] 1575 [743] 72
RGJF-09?ZCM?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11.5
1025 [484] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGJF-10?ZCM?
1 23800 [7.0] 14200 [4.2]
44500 [13.0] 15 11.5
1050 [495] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGJF-12?RCM?
1 25500 [7.5] 13500 [4.0]
45000 [13.2] 15 11.5
1200 [566] 72
2 29900 [8.8] 15100 [4.4] 1575 [743] 72
RGLE-07?BRQ?
1 23700 [6.9] 14300 [4.2]
45000 [13.2] 15.5 11.5
1025 [484] 72
2 28700 [8.4] 16300 [4.8] 1400 [661] 72
RGLE-10?BRM?
1 24300 [7.1] 14200 [4.2]
45000 [13.2] 15.5 12
1050 [495] 72
2 28700 [8.4] 16300 [4.8] 1400 [661] 72
RGLE-12?ARM?
1 24400 [7.1] 14100 [4.1]
45000 [13.2] 15.5 12
1075 [507] 72
2 28900 [8.5] 16100 [4.7] 1425 [672] 72
RGPE-07?BRQ?
1 23800 [7.0] 14200 [4.2]
45000 [13.2] 15.5 11.5
1050 [495] 72
2 28700 [8.4] 16300 [4.8] 1400 [661] 72
RGPE-10?BRM?
1 25700 [7.5] 13300 [3.9]
45500 [13.3] 15.5 11.5
1225 [578] 72
2 30400 [8.9] 15100 [4.4] 1625 [767] 72
RGPE-12?ARM?
1 24400 [7.1] 14100 [4.1]
45000 [13.2] 15.5 12
1075 [507] 72
2 28900 [8.5] 16100 [4.7] 1425 [672] 72
RGRM-07?YBG?
1 23600 [6.9] 14200 [4.2]
43500 [12.7] 14 10.5
1050 [495] 72
2 27200 [8.0] 16300 [4.8] 1400 [661] 72
RGRM-09?ZAJ?
1 23900 [7.0] 14100 [4.1]
44500 [13.0] 15 11
1075 [507] 72
2 28200 [8.3] 16300 [4.8] 1400 [661] 72
RGRM-10?ZAJ?
1 23700 [6.9] 14300 [4.2]
44500 [13.0] 15 11
1025 [484] 72
2 28400 [8.3] 16100 [4.7] 1425 [672] 72
RGRM-12?RAJ?
1 23900 [7.0] 14100 [4.1]
45000 [13.2] 15 11.5
1075 [507] 72
2 28900 [8.5] 16100 [4.7] 1425 [672] 72
RGTM-07?RBG?
1 24600 [7.2] 13900 [4.1]
45000 [13.2] 15 11.5
1125 [531] 72
2 29200 [8.6] 15800 [4.6] 1475 [696] 72
Rev.
5/8/2012
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions