Specification Sheet
Air
Performance Data
RARL- JEC Series
26
Outdoor
Unit
RARL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
061JEC
RCFL-H*6024
RGPE-10?BRM?
1 32900 [9.6] 15600 [4.6]
58000 [17.0] 16 12.5
1225 [578] 76
2 40400 [11.8] 17600 [5.2] 1625 [767] 78
RGPE-12?ARM?
1 32800 [9.6] 15700 [4.6]
58000 [17.0] 16 12.5
1200 [566] 76
2 40400 [11.8] 17600 [5.2] 1625 [767] 78
RGRM-07?YBG?
1 31800 [9.3] 15700 [4.6]
56000 [16.4] 15 11
1200 [566] 76
2 38000 [11.1] 18000 [5.3] 1575 [743] 78
RGRM-09?ZAJ?
1 32400 [9.5] 15600 [4.6]
57000 [16.7] 15.5 11.5
1225 [578] 76
2 39400 [11.5] 17600 [5.2] 1625 [767] 78
RGRM-10?ZAJ?
1 31500 [9.2] 16000 [4.7]
57000 [16.7] 16 11.5
1150 [543] 76
2 39200 [11.5] 17800 [5.2] 1600 [755] 78
RGRM-12?RAJ?
1 32400 [9.5] 15600 [4.6]
57500 [16.8] 16 12
1225 [578] 76
2 39900 [11.7] 17600 [5.2] 1625 [767] 78
RGTM-07?RBG?
1 34100 [10.0] 14900 [4.4]
58000 [17.0] 16 12
1325 [625] 76
2 40800 [12.0] 17200 [5.0] 1675 [790] 78
RGTM-09?ZAJ?
1 33100 [9.7] 15400 [4.5]
57500 [16.8] 16 12
1250 [590] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RGTM-10?RBJ?
1 33200 [9.7] 15300 [4.5]
58000 [17.0] 16 12.5
1275 [602] 76
2 40800 [12.0] 17200 [5.0] 1675 [790] 78
ROCA-070E04
1 32300 [9.5] 15700 [4.6]
56500 [16.6] 16 12
1200 [566] 76
2 37100 [10.9] 19400 [5.7] 1400 [661] 78
ROLA-070E04
1 32100 [9.4] 15900 [4.7]
57500 [16.8] 16 12
1175 [554] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
ROLA-115E05
1 32800 [9.6] 15700 [4.6]
57500 [16.8] 16 12.5
1200 [566] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RCFL-H*6024+RXMD-C06 Coil Only
1 33100 [9.7] 14900 [4.4]
58000 [17.0] 15 12
1325 [625] 76
2 40800 [12.0] 17200 [5.0] 1675 [790] 78
RCFN-H*6024
RGFE-09?ZCM?
1 32300 [9.5] 15700 [4.6]
57500 [16.8] 16 12
1200 [566] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RGFE-10?ZCM?
1 32400 [9.5] 15600 [4.6]
57000 [16.7] 16 12
1225 [578] 76
2 39200 [11.5] 17800 [5.2] 1600 [755] 78
RGFE-12?RCM?
1 32900 [9.6] 15600 [4.6]
57500 [16.8] 16 12
1225 [578] 76
2 39900 [11.7] 17600 [5.2] 1625 [767] 78
RGFG-09?ZCM?
1 32300 [9.5] 15700 [4.6]
57500 [16.8] 16 12
1200 [566] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RGFG-10?ZCM?
1 32300 [9.5] 15700 [4.6]
57500 [16.8] 16 12
1200 [566] 76
2 40100 [11.7] 17400 [5.1] 1650 [779] 78
RGFG-12?RCM?
1 32900 [9.6] 15600 [4.6]
57500 [16.8] 16 12
1225 [578] 76
2 39900 [11.7] 17600 [5.2] 1625 [767] 78
RGGE-10?ZCM?
1 32300 [9.5] 15700 [4.6]
57500 [16.8] 16 12
1200 [566] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RGGE-12?RCM?
1 34400 [10.1] 14600 [4.3]
58500 [17.1] 16 12
1375 [649] 76
2 42200 [12.4] 16300 [4.8] 1750 [826] 78
RGJF-09?ZCM?
1 32900 [9.6] 15600 [4.6]
57500 [16.8] 16 12
1225 [578] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
RGJF-10?ZCM?
1 32300 [9.5] 15700 [4.6]
57500 [16.8] 16 12
1200 [566] 76
2 39700 [11.6] 17800 [5.2] 1600 [755] 78
Rev.
5/8/2012
➀ Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions
Performance Data @ AHRI Standard Conditions—Cooling