Specification Sheet

Air
Performance Data
RARL- JEC Series
28
Outdoor
Unit
RARL-
Model Numbers
Stage
AHRI Cooling Performance
80°F [26.5°C] / 67°F [19.5°C] WB Indoor Air
95°F [35°C] DB Outdoor Air
Net
Sensible
BTU/H [kW]
Net
Latent
BTU/H [kW]
AHRI Ratings
Indoor Airflow
CFM [L/s]
Sound
Rating
dB
ID Coil ID Air Mover
Total Capacity
BTU/H [kW]
SEER EER
061JEC
RCQD-6024
RGJF-09?ZCM?
1 30100 [8.8] 14900 [4.4]
53500 [15.7] 15 11.5
1225 [578] 76
2 36400 [10.7] 17100 [5.0] 1600 [755] 78
RGJF-10?ZCM?
1 29900 [8.8] 15100 [4.4]
53500 [15.7] 15 11.5
1200 [566] 76
2 36400 [10.7] 17100 [5.0] 1600 [755] 78
RGJF-12?RCM?
1 31900 [9.3] 14100 [4.1]
54500 [16.0] 15 11.5
1375 [649] 76
2 38800 [11.4] 15700 [4.6] 1750 [826] 78
RGPE-07?BRQ?
1 30100 [8.8] 14900 [4.4]
54000 [15.8] 15 12
1225 [578] 76
2 36900 [10.8] 17100 [5.0] 1600 [755] 78
RGPE-10?BRM?
1 30100 [8.8] 14900 [4.4]
54000 [15.8] 15 12
1225 [578] 76
2 37100 [10.9] 16900 [5.0] 1625 [767] 78
RGPE-12?ARM?
1 29900 [8.8] 15100 [4.4]
54000 [15.8] 15.5 12
1200 [566] 76
2 37100 [10.9] 16900 [5.0] 1625 [767] 78
RGRM-07?YBG?
1 29400 [8.6] 15100 [4.4]
52000 [15.2] 13.5 10
1200 [566] 76
2 34800 [10.2] 17200 [5.0] 1575 [743] 78
RGRM-09?ZAJ?
1 30100 [8.8] 14900 [4.4]
53000 [15.5] 14.5 11
1225 [578] 76
2 36100 [10.6] 16900 [5.0] 1625 [767] 78
RGRM-10?ZAJ?
1 29200 [8.6] 15300 [4.5]
53000 [15.5] 14.5 11
1150 [543] 76
2 35900 [10.5] 17100 [5.0] 1600 [755] 78
RGRM-12?RAJ?
1 30100 [8.8] 14900 [4.4]
53500 [15.7] 15 11.5
1225 [578] 76
2 36600 [10.7] 16900 [5.0] 1625 [767] 78
RGTM-07?RBG?
1 31100 [9.1] 14400 [4.2]
54000 [15.8] 14.5 11.5
1325 [625] 76
2 37500 [11.0] 16500 [4.8] 1675 [790] 78
RGTM-09?ZAJ?
1 30200 [8.8] 14800 [4.3]
53500 [15.7] 15 11.5
1250 [590] 76
2 36400 [10.7] 17100 [5.0] 1600 [755] 78
RGTM-10?RBJ?
1 30900 [9.1] 14600 [4.3]
54000 [15.8] 15 11.5
1275 [602] 76
2 37500 [11.0] 16500 [4.8] 1675 [790] 78
ROCA-070E04
1 31600 [9.3] 13900 [4.1]
53000 [15.5] 14 11
1400 [661] 76
2 35900 [10.5] 17100 [5.0] 1600 [755] 78
ROLA-070E04
1 29800 [8.7] 15200 [4.5]
53500 [15.7] 15 11.5
1175 [554] 76
2 36400 [10.7] 17100 [5.0] 1600 [755] 78
ROLA-115E05
1 29900 [8.8] 15100 [4.4]
53500 [15.7] 15 11.5
1200 [566] 76
2 36400 [10.7] 17100 [5.0] 1600 [755] 78
RCQD-6024+RXMD-C06 Coil Only
1 30600 [9.0] 14400 [4.2]
54500 [16.0] 14 11.5
1325 [625] 76
2 38800 [11.4] 15700 [4.6] 1775 [838] 78
RCSL-H*6024 RHPL-HM6024
1 35000 [10.3] 14500 [4.2]
59000 [17.3] 16 13
1400 [661] 76
2 41900 [12.3] 17100 [5.0] 1700 [802] 78
Rev.
5/8/2012
Highest sales volume tested combination required by D.O.E. test procedures. [ ] Designates Metric Conversions