User Manual
Table Of Contents
- Contents
- About Your Water Heater
- Water Heater Application
- Model Type
- Mains Pressure
- Water Heater Operation
- Reduced Hot Water Flow When Heat Exchanger Is Cold
- Gas Boosting For A Solar Water Heater
- How Hot Should The Water Be?
- Hotter Water Increases The Risk Of Scald Injury
- Safety
- Warnings
- Precautions
- General Maintenance
- Minor Maintenance Every Six Months
- Major Service Every Five Years
- Circulated Hot Water Flow And Return System
- Going On Holidays
- To Turn Off The Water Heater
- To Turn On The Water Heater
- Frost Protection
- Draining The Water Heater
- How Do I Know If The Water Heater Is Installed Correctly?
- Victorian Customers
- Does The Water Chemistry Affect The Water Heater?
- How Long Will The Water Heater Last?
- Temperature Control
- Temperature Control – Standard
- Temperature Control – Deluxe
- Deluxe Controller Functions
- Deluxe Controller
- Voice Prompt And Operating Tone
- Assistance Call Function
- Temperature Settings – Deluxe Controllers
- Temperature Adjustment – Deluxe Controllers
- Kitchen Controller – Deluxe
- Bathroom Controllers – Deluxe
- Bath Fill Function
- Bath Fill Function – Brief Guide
- Bath Fill Function – Explanatory Notes
- Turning Off Bath Fill Function During Its Operation
- Notes on the Bath Fill function:
- Opening a Second Hot Water Tap During Bath Fill Operation
- Early Completion of Bath Fill Operation
- Interrupting Bath Fill Operation
- Operation of the Bath Fill function whilst a Deluxe Controller has priority
- Water Supplies
- Save A Service Call
- No Display On The Controller
- Cold Water From The Hot Tap
- Water Is Too Hot Or Not Hot Enough
- Reduced Hot Water Flow When Heat Exchanger Is Cold
- No Water From The Hot Tap
- Water Flow Fluctuates
- Gas Booster Operating Too Frequently
- Fan Continues To Run After Water Heater Operation Stops
- Clouds Of White ‘Vapour’ From The Flue Terminal
- Pressure Relief Valve Discharging
- Error Code
- Higher Than Expected Gas Bills
- Installation – Water Heater
- Installation Standards
- Water Heater Application
- Water Heater Location
- Installation Within A Covered Area
- Pipe Cover
- Recess Installation
- Frost Protection
- Mains Water Supply
- Hot Water Delivery
- Circulated Hot Water Flow And Return System
- Reducing Heat Losses
- Water Temperature Diagrams
- Technical Data
- Dimensions – Water Heater
- Dimensions – Standard Controllers
- Dimensions – Deluxe Controllers
- Typical Installation – Outdoor Location
- Connections – Plumbing
- Connections – Electrical
- EZ LINK System Dual Installation
- Installation – Controllers
- Commissioning
- Draining The Water Heater
- Rheem Continuous Flow Gas Water Heater Warranty – Australia and New Zealand Only
- 1. The Rheem Warranty – General
- 2. Terms Of The Rheem Warranty And Exclusions To It
- 3. What Is Covered By The Rheem Warranty For The Water Heaters Detailed In This Document
- 4. Entitlement To Make A Claim Under This Warranty
- 5. How To Make A Claim Under This Warranty
- 6. The Australian Consumer Law
75
COMMISSIONING
All water heaters are tested and adjusted before dispatch from the factory, however further adjustments may
become necessary because of local conditions.
TO TURN ON THE WATER HEATER
Open all of the hot taps in the house (don’t forget the shower).
Open the cold water isolation valve fully at the inlet to the water heater.
Air will be forced out of the taps.
Close each tap as water flows freely from it.
Check the pipe work for leaks.
Open the gas isolation valve fully.
Check the gas pipe work for leaks.
Plug in the water heater at the power outlet and switch on the electrical supply.
Turn on a controller, if one is fitted, by pressing the on / off ( ) button.
The on / off operating light and the priority light will both glow.
Open a hot tap.
The water heater will operate automatically.
Check to ensure the flow from each connected hot tap is sufficient to operate the water heater.
The minimum operating flow rate for all models is 2.0 litres per minute.
Check and if required adjust the preset outlet temperature setting of the water heater.
Refer to “Preset Outlet Temperature Setting” on page 79.
Check and if required adjust the outlet compensation temperature adjustment on an AU – 876 series or
NZ – 874 series water heater.
Refer to “Outlet Compensation Temperature Adjustment” on page 81.
The automatic water governor incorporated in the water heater is not adjustable.
To complete the installation, it is necessary to check the gas supply pressure at the inlet to the water heater
(refer to “Gas Inlet Pressure” on page 75), the minimum test point pressure and the maximum test point
pressure (refer to “Burner Gas Pressure” on page 77).
Upon completion and testing of the installation, ensure the controller(s) is turned off (if fitted). Explain to the
householder or a responsible officer the functions and operation of the water heater and the controllers (if
fitted).
Warning: Upon completion of the installation and commissioning of the water heater, leave this guide with
the householder or a responsible officer. DO NOT leave this guide inside of the cover of the water heater, as
it may interfere with the safe operation of the water heater or ignite when the water heater is turned on.
GAS INLET PRESSURE
IMPORTANT - CHECK the gas supply pressure at the inlet to the water heater with the water heater and all
other gas burning appliances in the premises operating (burners alight). The minimum gas supply pressure is:
Natural Gas 1.13 kPa Propane, LP Gas 2.75 kPa
If this minimum cannot be achieved, it may indicate the meter or the gas line to the water heater is undersized.
It is important to ensure that an adequate gas supply pressure is available to the water heater when other gas
burning appliances, on the same gas supply, are operating.
X 10L
88