Specification Sheet

Air
Gross Systems Performance Data
RGEA14 Series
37
GROSS SYSTEMS PERFORMANCE DATA—RGEA14030A
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s]
1100 [519] 1000 [472] 850 [401] 1100 [519] 1000 [472] 850 [401] 1100 [519] 1000 [472] 850 [401]
DR
0.16 0.15 0.11 0.16 0.15 0.11 0.16 0.15 0.11
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
37.0 [10.9]
21.6 [6.3]
1.7
36.4 [10.7]
20.6 [6.0]
1.6
35.4 [10.4]
19.2 [5.6]
1.6
35.0 [10.3]
25.6 [7.5]
1.7
34.4 [10.1]
24.4 [7.2]
1.6
33.4 [9.8]
22.7 [6.7]
1.6
33.2 [9.7]
28.8 [8.4]
1.6
32.6 [9.6]
27.5 [8.1]
1.6
31.7 [9.3]
25.6 [7.5]
1.6
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.0 [10.5]
21.1 [6.2]
1.7
35.4 [10.4]
20.1 [5.9]
1.7
34.4 [10.1]
18.7 [5.5]
1.7
33.9 [9.9]
25.1 [7.4]
1.7
33.3 [9.8]
24.0 [7.0]
1.7
32.4 [9.5]
22.3 [6.5]
1.7
32.2 [9.4]
28.3 [8.3]
1.7
31.6 [9.3]
27.0 [7.9]
1.7
30.7 [9.0]
25.1 [7.4]
1.7
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
34.9 [10.2]
20.6 [6.0]
1.8
34.3 [10.1]
19.7 [5.8]
1.8
33.4 [9.8]
18.3 [5.4]
1.8
32.9 [9.6]
24.6 [7.2]
1.8
32.3 [9.5]
23.5 [6.9]
1.8
31.4 [9.2]
21.8 [6.4]
1.8
31.1 [9.1]
27.8 [8.1]
1.8
30.6 [9.0]
26.5 [7.8]
1.8
29.7 [8.7]
24.7 [7.2]
1.8
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
33.9 [9.9]
20.1 [5.9]
1.9
33.3 [9.7]
19.2 [5.6]
1.9
32.3 [9.5]
17.8 [5.2]
1.9
31.8 [9.3]
24.1 [7.1]
1.9
31.2 [9.2]
23.0 [6.7]
1.9
30.4 [8.9]
21.4 [6.3]
1.9
30.0 [8.8]
27.3 [8.0]
1.9
29.5 [8.6]
26.0 [7.6]
1.9
28.7 [8.4]
24.2 [7.1]
1.9
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
32.8 [9.6]
19.5 [5.7]
2.1
32.2 [9.4]
18.6 [5.5]
2.0
31.3 [9.2]
17.3 [5.1]
2.0
30.7 [9.0]
23.5 [6.9]
2.0
30.2 [8.8]
22.5 [6.6]
2.0
29.3 [8.6]
20.9 [6.1]
2.0
28.9 [8.5]
26.7 [7.8]
2.0
28.4 [8.3]
25.5 [7.5]
2.0
27.6 [8.1]
23.7 [7.0]
2.0
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
31.6 [9.3]
18.9 [5.5]
2.2
31.1 [9.1]
18.1 [5.3]
2.2
30.2 [8.9]
16.8 [4.9]
2.1
29.6 [8.7]
22.9 [6.7]
2.2
29.1 [8.5]
21.9 [6.4]
2.1
28.3 [8.3]
20.4 [6.0]
2.1
27.8 [8.2]
26.1 [7.7]
2.2
27.3 [8.0]
25.0 [7.3]
2.1
26.6 [7.8]
23.2 [6.8]
2.1
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
30.5 [8.9]
18.3 [5.4]
2.3
30.0 [8.8]
17.5 [5.1]
2.3
29.2 [8.5]
16.3 [4.8]
2.3
28.5 [8.3]
22.3 [6.5]
2.3
28.0 [8.2]
21.3 [6.2]
2.3
27.2 [8.0]
19.8 [5.8]
2.2
26.7 [7.8]
25.5 [7.5]
2.3
26.2 [7.7]
24.4 [7.1]
2.3
25.5 [7.5]
22.7 [6.6]
2.2
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
29.4 [8.6]
17.7 [5.2]
2.4
28.8 [8.5]
16.9 [5.0]
2.4
28.1 [8.2]
15.7 [4.6]
2.4
27.3 [8.0]
21.7 [6.4]
2.4
26.8 [7.9]
20.7 [6.1]
2.4
26.1 [7.6]
19.3 [5.6]
2.4
25.5 [7.5]
24.9 [7.3]
2.4
25.1 [7.4]
23.8 [7.0]
2.4
24.4 [7.2]
22.1 [6.5]
2.4
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
28.2 [8.3]
17.0 [5.0]
2.6
27.7 [8.1]
16.3 [4.8]
2.6
26.9 [7.9]
15.1 [4.4]
2.5
26.1 [7.7]
21.0 [6.2]
2.6
25.7 [7.5]
20.1 [5.9]
2.6
25.0 [7.3]
18.7 [5.5]
2.5
24.4 [7.1]
24.2 [7.1]
2.6
23.9 [7.0]
23.1 [6.8]
2.5
23.3 [6.8]
21.5 [6.3]
2.5
120
[48.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
27.0 [7.9]
16.3 [4.8]
2.7
26.5 [7.8]
15.6 [4.6]
2.7
25.8 [7.6]
14.5 [4.3]
2.7
25.0 [7.3]
20.3 [6.0]
2.7
24.5 [7.2]
19.4 [5.7]
2.7
23.9 [7.0]
18.1 [5.3]
2.7
23.2 [6.8]
23.2 [6.8]
2.7
22.8 [6.7]
22.5 [6.6]
2.7
22.2 [6.5]
20.9 [6.1]
2.7
125
[51.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
25.8 [7.6]
15.6 [4.6]
2.9
25.4 [7.4]
14.9 [4.4]
2.9
24.7 [7.2]
13.9 [4.1]
2.8
23.8 [7.0]
19.6 [5.8]
2.9
23.3 [6.8]
18.8 [5.5]
2.9
22.7 [6.7]
17.4 [5.1]
2.8
22.0 [6.4]
22.0 [6.4]
2.9
21.6 [6.3]
21.6 [6.3]
2.9
21.0 [6.2]
20.3 [5.9]
2.8
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions