Specification Sheet

Air
Gross Systems Performance Data
RGEA15 Series
43
GROSS SYSTEMS PERFORMANCE DATA—RGEA15030A
ENTERING INDOOR AIR @ 80°F [26.7°C] dbE
wbE 71°F [21.7°C] 67°F [19.4°C] 63°F [17.2°C]
CFM [L/s]
1070 [505] 975 [460] 830 [392] 1070 [505] 975 [460] 830 [392] 1070 [505] 975 [460] 830 [392]
DR
0.16 0.14 0.1 0.16 0.14 0.1 0.16 0.14 0.1
O
U
T
D
O
O
R
D
R
Y
B
U
L
B
T
E
M
P
E
R
A
T
U
R
E
°F
[°C]
75
[23.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
36.8 [10.8]
21.5 [ 6.3]
1.7
36.1 [10.6]
20.5 [ 6.0]
1.7
35.2 [10.3]
19.1 [ 5.6]
1.6
34.3 [10.1]
25.1 [ 7.4]
1.7
33.7 [9.9]
24.0 [7.0]
1.6
32.8 [9.6]
22.4 [6.6]
1.6
32.4 [9.5]
28.3 [8.3]
1.6
31.8 [9.3]
27.1 [7.9]
1.6
31.0 [9.1]
25.2 [7.4]
1.6
80
[26.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
35.7 [10.5]
21.0 [ 6.1]
1.8
35.1 [10.3]
20.1 [ 5.9]
1.7
34.2 [10.0]
18.7 [ 5.5]
1.7
33.3 [ 9.7]
24.7 [ 7.2]
1.7
32.7 [9.6]
23.6 [6.9]
1.7
31.8 [9.3]
21.9 [6.4]
1.7
31.3 [9.2]
27.8 [8.2]
1.7
30.8 [9.0]
26.6 [7.8]
1.7
30.0 [8.8]
24.8 [7.3]
1.7
85
[29.4]
Total BTUH [kW]
Sens BTUH [kW]
Power
34.7 [10.2]
20.5 [ 6.0]
1.9
34.1 [10.0]
19.6 [ 5.7]
1.8
33.2 [ 9.7]
18.2 [ 5.3]
1.8
32.2 [ 9.4]
24.2 [ 7.1]
1.8
31.7 [9.3]
23.1 [6.8]
1.8
30.8 [9.0]
21.5 [6.3]
1.8
30.3 [8.9]
27.4 [8.0]
1.8
29.8 [8.7]
26.2 [7.7]
1.8
29.0 [8.5]
24.3 [7.1]
1.8
90
[32.2]
Total BTUH [kW]
Sens BTUH [kW]
Power
33.7 [ 9.9]
20.0 [ 5.9]
2.0
33.1 [ 9.7]
19.1 [ 5.6]
1.9
32.2 [ 9.4]
17.8 [5.2]
1.9
31.2 [ 9.1]
23.6 [ 6.9]
1.9
30.6 [9.0]
22.6 [6.6]
1.9
29.8 [8.7]
21.0 [6.2]
1.9
29.2 [8.6]
26.8 [7.9]
1.9
28.7 [8.4]
25.7 [7.5]
1.9
28.0 [8.2]
23.9 [7.0]
1.9
95
[35]
Total BTUH [kW]
Sens BTUH [kW]
Power
32.6 [ 9.5]
19.4 [ 5.7]
2.1
32.0 [ 9.4]
18.6 [ 5.4]
2.1
31.2 [ 9.1]
17.3 [ 5.1]
2.0
30.1 [ 8.8]
23.1 [ 6.8]
2.1
29.6 [8.7]
22.1 [6.5]
2.0
28.8 [8.4]
20.5 [6.0]
2.0
28.2 [8.3]
26.3 [7.7]
2.0
27.7 [8.1]
25.1 [7.4]
2.0
26.9 [7.9]
23.4 [6.9]
2.0
100
[37.8]
Total BTUH [kW]
Sens BTUH [kW]
Power
31.5 [ 9.2]
18.8 [ 5.5]
2.2
31.0 [ 9.1]
18.0 [ 5.3]
2.2
30.1 [ 8.8]
16.8 [ 4.9]
2.1
29.0 [ 8.5]
22.5 [ 6.6]
2.2
28.5 [8.4]
21.5 [6.3]
2.2
27.7 [8.1]
20.0 [5.9]
2.1
27.1 [7.9]
25.7 [7.5]
2.2
26.6 [7.8]
24.6 [7.2]
2.1
25.9 [7.6]
22.9 [6.7]
2.1
105
[40.6]
Total BTUH [kW]
Sens BTUH [kW]
Power
30.4 [ 8.9]
18.2 [ 5.3]
2.3
29.9 [ 8.8]
17.4 [ 5.1]
2.3
29.1 [ 8.5]
16.2 [ 4.8]
2.3
27.9 [ 8.2]
21.9 [ 6.4]
2.3
27.4 [8.0]
20.9 [6.1]
2.3
26.7 [7.8]
19.5 [5.7]
2.3
26.0 [7.6]
25.1 [7.4]
2.3
25.6 [7.5]
24.0 [7.0]
2.3
24.9 [7.3]
22.3 [6.5]
2.2
110
[43.3]
Total BTUH [kW]
Sens BTUH [kW]
Power
29.3 [ 8.6]
17.6 [ 5.2]
2.5
28.8 [ 8.4]
16.8 [ 4.9]
2.4
28.0 [ 8.2]
15.7 [ 4.6]
2.4
26.8 [ 7.9]
21.3 [ 6.2]
2.4
26.4 [7.7]
20.3 [6.0]
2.4
25.6 [7.5]
18.9 [5.5]
2.4
24.9 [7.3]
24.4 [7.2]
2.4
24.5 [7.2]
23.4 [6.9]
2.4
23.8 [7.0]
21.8 [6.4]
2.4
115
[46.1]
Total BTUH [kW]
Sens BTUH [kW]
Power
28.2 [ 8.3]
16.9 [ 5.0]
2.6
27.7 [ 8.1]
16.2 [ 4.7]
2.6
27.0 [ 7.9]
15.1 [ 4.4]
2.5
25.7 [ 7.5]
20.6 [ 6.0]
2.6
25.3 [7.4]
19.7 [5.8]
2.6
24.6 [7.2]
18.3 [5.4]
2.5
23.8 [7.0]
23.8 [7.0]
2.6
23.4 [6.8]
22.7 [6.7]
2.6
22.7 [6.7]
21.2 [6.2]
2.5
120
[48.9]
Total BTUH [kW]
Sens BTUH [kW]
Power
27.1 [ 7.9]
16.2 [ 4.8]
2.8
26.6 [ 7.8]
15.5 [ 4.5]
2.7
25.9 [ 7.6]
14.4 [ 4.2]
2.7
24.6 [ 7.2]
19.9 [ 5.8]
2.7
24.2 [7.1]
19.0 [5.6]
2.7
23.5 [6.9]
17.7 [5.2]
2.7
22.7 [6.6]
22.7 [6.6]
2.7
22.3 [6.5]
22.1 [6.5]
2.7
21.7 [6.3]
20.5 [6.0]
2.7
125
[51.7]
Total BTUH [kW]
Sens BTUH [kW]
Power
25.9 [ 7.6]
15.5 [ 4.5]
2.9
25.5 [ 7.5]
14.8 [ 4.3]
2.9
24.8 [ 7.3]
13.8 [ 4.0]
2.8
23.4 [ 6.9]
19.2 [ 5.6]
2.9
23.0 [6.7]
18.3 [5.4]
2.9
22.4 [6.6]
17.1 [5.0]
2.8
21.5 [6.3]
21.5 [6.3]
2.9
21.1 [6.2]
21.1 [6.2]
2.9
20.6 [6.0]
19.9 [5.8]
2.8
DR —Depression ratio
dbE —Entering air dry bulb
wbE—Entering air wet bulb
Total —Total capacity x 1000 BTUH
Sens —Sensible capacity x 1000 BTUH
Power —KW input
NOTES: When the entering air dry bulb is other than 80°F [27°C], adjust the sensible
capacity from the table by adding [1.10 x CFM x (1 – DR) x (dbE – 80)].
[ ] Designates Metric Conversions