Instructions / Assembly

AP18733 REV. 3.2.17
58
CURRENT TIME : AM 1:39
CURRENT DAY : MONDAY
TIMER SETTING : MONDAY 5:00~6:30 , 18:00~20:00
DESIRED HOT WATER TEMPERATURE : 120
°F
Figure 34 – Example Display
C. START-UP SEQUENCE
After the appliance is powered ON, the LCD display shows a sequence of information. The icons will ash, followed by various indicators that
describe the appliance controller and software versions. It will take the appliance roughly 15 seconds to cycle through the Start-Up Sequence.
Display Items Time for Display Remarks
LCD Test
1 Sec All segments “ON”
0.5 Sec All segments “OFF”
Category: 199
1 Sec Pdn
1 Sec 0061
Software Version for Front Panel
1 Sec SPn
1 Sec 00.XX
Software Version for Water Heater
1 Sec SFn
1 Sec XX.XX
Hardware Version for Water Heater
1 Sec Hdn
1 Sec 00XX
Table 24 – Start-Up Sequence
The Control System can operate through user and service modes that have specic LCD outputs and dedicated controls, including:
Changing the Set-Point Temperature
Error Mode
Status Display Mode
Installer Mode
High Elevation Mode
High Temperature Mode
NOTE: The Control System will not allow changes if Lock Mode is activated unless the button is pressed for more than 5 seconds.
D. CHANGING THE DHW SET-POINT
NOTE: The setpoint cannot be changed if water is owing through the unit. Ensure there is no demand on the water heater when
changing setpoint.
The display shows the icon when the DHW set-point can be changed.