Instructions / Assembly

34
User Interface
BASIC SETTINGS: The basic settings in you water heater
can allow you to change the temperature unit, screen
adjustment lock/unlock, enabling/disabling the alarm
beep, and your EcoNet network instance. Simply select
the setting by tapping it, and press the Up/Down arrows
to make adjustments. WiFi setup can be accessed from
this screen as well.
CONFIGURATION SETTINGS: The configuration settings
on your water heater allows you to control the differen-tial
temperature set point, turning on/off the recircula-tion
pump, auxiliary input/output, enabling/disabling
modulation, and how your hot water heater reacts to a
detected leak.
The setting can be highlighted by tapping and then ad-
justed with the up/down arrows.
The Differential can be adjusted from 1°F to 30°F. The
recommended differential is 12°F.
This water heater has a modulation algorithm that can
be disabled by tapping ‘No’ in front of Modulation Dis-
abled and making adjustments by tapping the up/down
buttons.
Water heater behavior in response to leak can be
changed from Alarm Only to Disable When Leak De-
tected.
Shutoff Valve (on premium models only) behavior re-
sponse can be selected to the following:
• Open
• Closed
Close if Leak Detected: Always close the valve when
leak is detected.
Close if Unocc. Leak Detected (based on unoccupied
times from the schedule function). Water heater will
alarm only during the operating hours.
SCHEDULE SETTINGS: The schedule settings allows you
to control when your hot water heater will be enabled/
disabled. Your heater allows you to select a day you
want and set the times when the heater will be in use.
You can also copy/paste the day you select and apply
it to other days as well.
TIME/DATE SETTINGS: By selecting time/date you can
change the water heaters current set time. You can also
select the daylight savings time function to automati-
cally adjust the time for daylight savings.
BacNet
This water heater is compatible with BacNet MS/TP
protocol. Please refer to the GHE BacNet instruction
sheet for details on the setup.
basic settings
Temperature Display
Screen Adjustment Lock?
Beep On Alarm
EcoNet Network Instance
Elevation
Fahrenheit
No
Enabled
1
Normal
config. settings
Differential Temp Setpt.
Recirc. Pump Config
Aux Input Select
Aux Output Select
Modulation Disabled?
When Leak Detected
12.0° F
Off
Flow Sensor
None
No
Alarm Only
schedule settings
Wed. Jan.11, 2:49 pm
Morning:
Night:
Mon.
08:00 am
06:00 pm
Time
Occupied
Occupied
Schedule
Tue.
copy
day
paste
day
cancel
Wed. Thu. Fri. Sat. Sun.
set te time and date
accept
D.S.T.
enabled
:
10 54 am
:
Jan. 11 2017
The up/down arrows enable
you to adjust the time of the
morning/night run times.
By selecting a day and then access-
ing the copy function, you can
paste that day’s settings onto other
The up/down arrows allow
you to control the time,
month, day, and year.
The D.S.T function allows you to
adjust the time for daylight sav-
ings time.