Read these instructions thoroughly and make
sure you understand all steps and procedures
before proceeding with the installation.
Determine the location for the concentric termi-
nal then make a 5 in. (12.7 cm) hole through the
exterior wall.
Disassemble the concentric terminal assembly.
Note: The concentric terminal assembly
consists of an inner, straight vent pipe, an
outer, straight combustion air-inlet pipe, a
Wye tting and rain cap.
The concentric terminal assembly is designed to
accept 3 in. (7.6 cm) diameter pipe.
If 2 in. (5.1 cm) diameter pipe is used:
Then either 2 in. x 3 in. (5.1 cm x 7.6 cm)
pipe increasers,
Or ush bushings must be installed to the
vent and combustion air-inlet connections of
the terminal assembly.
DO NOT use the concentric terminal assem-
bly with 4 in. (10.2 cm) vent and combustion
air-inlet systems.
From inside the building, insert the outer,
straight combustion air-inlet pipe through the
wall so that the rear of the rain cap when in-
stalled sits ush with the outside wall.
NOTICE: The concentric terminal assembly
may be reduced in length as follows:
Measure for desired installation length then
cut the outer, straight combustion air-inlet
pipe accordingly but not less than 12 in. (30
cm).
Measure and cut the straight inner vent pipe
of the concentric terminal assembly so it
is 13 in. (5.1 cm) longer in length than the
outer, straight combustion air-inlet pipe.
Ensure that there is no insulation or debris in
the pipe.
Assemble the vent pipe assembly.
Clean and cement the rain cap to the inner,
straight vent pipe.
From the outside, slide the vent pipe with
rain cap assembly through the combustion
air-inlet pipe until the rear of the rain cap is
ush with the outside wall.
Clean and cement the rain cap to the combus-
tion air-inlet pipe.
Clean and cement a 3 in. (7.6 cm) diameter,
ULC-S636 approved, Schedule 40, PVC,
90° street elbow to the rain cap.
From the inside, clean and cement the wye t-
ting to the vent and combustion air-inlet pipes of
the termination assembly.
Complete the installation of the remainder of the
vent system and attach it to the vent connector
tting on the water heaters blower assembly.
IMPORTANT: Raise all horizontal sections
upwards a minimum of 1/8 in. per foot
(10 mm per m).
DO NOT use unequal diameters of pipe and
ttings for the vent and combustion air-inlet
systems except as dened previously
NOTICE: The difference between the vent
and combustion air-inlet system equivalent
lengths must be no greater than 5 ft. (1.5 m).
Complete the installation of the remainder of the
combustion air-inlet system and attach it to the
combustion air-inlet connector tting on the wa-
ter heaters combustion air-inlet tube assembly.
Support vertical and horizontal lengths of the
vent and combustion air-inlet systems as previ-
ously mentioned.
IMPORTANT: Ensure that all the coupling
clamps are tight before allowing the water heater
to operate.
Horizontal Vent- Alternate Concentric Terminal Installation:
Contact Manufacturer's National Service Department for Kit information, see "If You Need Service"
section.