Air Air Conditioners RA14 Series Rheem Classic® Series Air Conditioners RA14 Series Efficiencies up to 16 SEER/13 EER Nominal Sizes 11/2 to 5 Ton [5.28 to 17.6 kW] Cooling Capacities 17.3 to 60.5 kBTU [5.7 to 17.7 kW] 16.0 “Proper sizing and installation of equipment is critical to achieve optimal performance. Ask your Dealer for details or visit www.energystar.gov.
Air Table of Contents RA14 Series TABLE OF CONTENTS Standard Feature ......................................................................................................3 Available SKUs ........................................................................................................3 Features & Benefits ..............................................................................................4-5 Model Number Identification ......................................................................
Air Standard Feature/Available SKUs RA14 Series Standard Feature Table STANDARD FEATURES Feature R-410a Refrigerant Maximum SEER Maximum EER Scroll Compressor Field Installed Filter Drier Front Seating Service Valves Internal Pressure Relief Valve Internal Thermal Overload Long Line capability Low Ambient capability with Kit 3-4-5 Expanded Valve Space Composite Basepan 2 Screw Control Box Access 15" Access to Internal Components Quick release louver panel design No fasteners to remove along bottom Optimiz
Air Features & Benefits RA14 Series Introduction to RA14 Air Conditioner The RA14 is our 14 SEER air conditioner and is part of the Rheem air conditioner product line that extends from 13 to 20 SEER. This highly featured and reliable air conditioner is designed for years of reliable, efficient operation when matched with Rheem indoor aluminum evaporator coils and furnaces or air handler units with aluminum evaporators.
Air The entire cabinet has powder post paint ( 20 ) achieving 1000 hour salt spray rating, allowing the cabinet to retain its aesthetics throughout its life.
A 14 Product Category P - Heat Pump Brand 13 - 13 SEER 14 - 14 SEER 16 - 16 SEER 17 - 17 SEER 20 - 20 SEER SEER 14 Product Category C - Evap Coil Brand F - Furn Coil H - Air-Handler Coil Type F [ ] Designates Metric Conversions Rheem C R Furnace Coils (For Reference) Rheem A R Heat Pumps (For Reference) A J 1 N A * 24 Capacity BTU/HR 18 - 18,000 [5.28 kW] 24 - 24,000 [7.03 kW] 30 - 30,000 [8.79 kW] 36 - 36,000 [10.55 kW] 42 - 42,000 [12.31 kW] 48 - 48,000 [14.
V - Variable speed T - Constant Torque (X-13) P - PSC 90 - 90 AFUE 92 - 92 AFUE 95 - 95 AFUE 96 - 96 AFUE 97 - 97 AFUE Rheem A - 1st Design Major Rev A 1 - Single-stage 2 - Two-stage 80 - 80+ AFUE Rheem H T Motor V Capacity BTU/HR 24 - 24,000 [7.03 kW] 36 - 36,000 [10.55 kW] 48 - 48,000 [14.07 kW] 60 - 60,000 [17.58 kW] 36 70 Stages 2 Coil Size S - Standard Eff. M -Mid Eff. H - High Eff. 14 - 14" 17 - 17.5" 21 - 21" 24 - 24.
Air General Data/Electrical Data RA14 Series Physical Data Model No. Nominal Tonnage Valve Connections Liquid Line O.D. – in. Suction Line O.D. – in. Refrigerant (R410A) furnished oz.¹ Compressor Type Outdoor Coil Net face area – Outer Coil Net face area – Inner Coil Tube diameter – in. Number of rows Fins per inch Outdoor Fan Diameter – in. Number of blades Motor hp CFM RPM watts Shipping weight – lbs. Operating weight – lbs. RA1418A 1.5 PHYSICAL DATA RA1424A RA1430A 2.0 2.5 RA1436A 3.0 RA1442A 3.
Air Accessories/Weighted Sound Power/Thermostats RA14 Series Accessories Model No.
Air Unit Dimensions RA14 Series Unit Dimensions OPERATING MODEL NO. H (Height) L (Length) SHIPPING W (Width) H (Height) L (Length) W (Width) INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm INCHES mm RA1418 25 635 29.75 755 29.75 755 26.75 679 32.38 822 32.38 822 RA1424 25 635 29.75 755 29.75 755 26.75 679 32.38 822 32.38 822 RA1430 27 685 29.75 755 29.75 755 28.75 679 32.38 822 32.38 822 RA1436 27 685 33.75 857 33.75 857 28.75 730 36.
24⬙ (609.6) Service 6⬙ (152.4) 24⬙ (609.6) 24⬙ recommended 12⬙ minimum 12⬙ (304.8) 6⬙ (152.4) 24⬙ (609.6) Service WALL 12⬙ (304.8) 24⬙ (609.6) 24⬙ recommended 12⬙ minimum IMPORTANT: When installing multiple units in an alcove, roof well or partially enclosed area, ensure there is adequate ventillation to prevent re-circulation of discharge air. NOTE: NUMBERS IN () = mm 18⬙ (457.2) 24⬙ (609.6) Service WALL CLEARANCES WALL 24⬙ (609.6) Service 12⬙ (304.8) 24⬙ (609.
Air Wiring Diagram/Application Guidelines RA14 Series Control Wiring FIGURE 2 *IF MAXIMUM OUTLET TEMPERATURE RISE IS DESIRED, IT IS RECOMMENDED THAT CONTROL WIRING FOR GAS OR OIL FURNACE W1 (W/BK) AND W2 (W/BL) BE JUMPERED TOGETHER.
Liquid Line Selection Chart Elevation (Above or Below) Indoor Coil Total Equivalent Length - Feet [m] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 3/8" [9.53] 24 30 36 42 48 60 [6.1] N/R N/R N/R N/R 25 [7.62] 50 [15.24] 55 [16.76] 25 [7.62] 50 [15.24] 60 [18.29] 1/2 [12.71] 60 [18.29] 50 [15.24] 25 [7.62] N/R N/R 80 [24.38] 75 [22.86] 55 [16.76] 45 [13.72] 15 [4.57] N/R N/R 80 [24.38] 70 [21.34] 50 [15.24] N/R N/R 55 [16.76] N/R 85 [25.91] 75 [22.
3/4" [19.06] 3/4" [19.06] 3/4" [19.06] 7/8" [22.23] 7/8" [22.23] 7/8" [22.23] 24 30 36 42 48 60 NOTES: N/R = Application not recommended. All calculations assume a 3/8" liquid line 3/4" [19.06] 18 R-410A System Capacity Model 1.00 N/R N/R N/R 1.00 1.01 1.00 N/R N/R 0.98 1.00 N/R N/R N/R 0.99 1.00 1.00 N/R N/R 1.00 3/4 [19.05] 7/8 [22.23] 1 [25.4] 1-1/8 [28.58] 5/8 [15.88] 3/4 [19.05] 1 [25.4] 1-1/8 [28.58] 5/8 [15.88] 3/4 [19.05] N/R 0.95 0.98 1.00 1.00 1.00 0.94 0.98 0.99 1.00 1.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling High Sales Volume Tested Combination (HSVTC) Outdoor Unit Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1418AJ1 RCF2417STAM 17800 [5.2] 13400 [3.9] 4400 [1.3] 14 11.5 600 [283.2] 7489162 RA1424AJ1 RCF2417STAM 24000 [7.0] 18100 [5.3] 5900 [1.7] 14 11.5 800 [377.6] 7489163 RA1430AJ1 RCF3617STAM 28800 [8.4] 21800 [6.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) Coil Only Ratings Outdoor Unit Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] RCF2414STAM+RXMD-C04 17900 [5.2] 13100 [3.8] RCF2417HTAM+RXMD-C04 17900 [5.2] RCF2417MTAM+RXMD-C04 17900 [5.2] RCF2421MTAM+RXMD-C04 Indoor CFM [L/s] SEER EER 4800 [1.4] 14 11.5 600 [283.2] 7490519 13100 [3.8] 4800 [1.4] 14 11.5 600 [283.2] 7493620 13100 [3.8] 4800 [1.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPT: Single Stage Upflow Constant Torque 80% Furnace Ratings Outdoor Unit RA1418AJ1 Furnace RGPT-05?BMK? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417HTAM 18500 [5.4] 14500 [4.2] RCF2417MTAM 18500 [5.4] 14500 [4.2] 4000 [1.2] 16 13 650 [306.8] 7490528 4000 [1.2] 16 13 650 [306.8] RCF2417STAM 18500 [5.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPT: Single Stage Upflow Constant Torque 80% Furnace Ratings Outdoor Unit RA1436AC1 RA1436AC1 RA1436AC1 RA1436AJ1 RA1436AJ1 RA1436AJ1 Furnace RGPT-07?BRQ? RGPT-10?BRM? RGPT-12?ARM? RGPT-05?BMK? RGPT-07?AMK? RGPT-07?BRQ? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF3621MTAM 36600 [10.7] 25200 [7.4] 11400 [3.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPT: Single Stage Upflow Constant Torque 80% Furnace Ratings Outdoor Unit RA1448AJ1 Furnace RGPT-07?BRQ? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF4821STAM 46000 [13.5] 33400 [9.8] 12600 [3.7] 14.5 RCF4824STAM 46000 [13.5] 33400 [9.8] 12600 [3.7] 14.5 12 1400 [660.7] 7492386 12 1400 [660.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPE: Two-Stage, Variable Speed 80% (upflow/horizontal) furnace with Comfort Control System Ratings Outdoor Unit RA1418AJ1 Furnace RGPE-05?BMK? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417HTAM 18200 [5.3] 14100 [4.1] RCF2417MTAM 18200 [5.3] 14100 [4.1] 4100 [1.2] 16 13 575 [271.4] 7490526 4100 [1.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPE: Two-Stage, Variable Speed 80% (upflow/horizontal) furnace with Comfort Control System Ratings Outdoor Unit Furnace Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1442AJ1 RGPE-05?BMK? RCF4821STAM 40500 [11.9] 28900 [8.5] 11600 [3.4] 14 11.5 1200 [566.3] 7492007 RA1442AJ1 RGPE-07?AMK? RCF4821STAM 41000 [12.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGPE: Two-Stage, Variable Speed 80% (upflow/horizontal) furnace with Comfort Control System Ratings Outdoor Unit RA1460AJ1 Furnace RGPE-12?ARM? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF6024HTAM 56500 [16.6] 38300 [11.2] 18200 [5.3] 14.5 RCF6024STAM 56500 [16.6] 38300 [11.2] 18200 [5.3] 14.5 12 1425 [672.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) R95T: 95% AFUE single-stage Constant Torque Multipoise Gas Furnace Ratings Outdoor Unit RA1418AJ1 RA1424AJ1 RA1424AJ1 Furnace R95TA0601317MSA R95TA0601317MSA R95TA0701317MSA Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417MTAM 18700 [5.5] 14800 [4.3] 3900 [1.1] 15.5 13 700 [330.4] 7490533 RCF2417STAM 18700 [5.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) R95T: 95% AFUE single-stage Constant Torque Multipoise Gas Furnace Ratings Outdoor Unit Furnace Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1442AJ1 R95TA0701317MSA RCF4821STAM 40500 [11.9] 28500 [8.4] 12000 [3.5] 14 11.5 1125 [530.9] 7491996 RCF4821STAM 41500 [12.2] 30600 [9.0] 10900 [3.2] 14 12.2 1325 [625.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) R96V: 96% AFUE 2-stage Variable Speed Multipoise Gas Furnace Ratings Outdoor Unit RA1418AJ1 Furnace R96VA0602317MSA Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417HTAM 18700 [5.5] 14800 [4.3] 3900 [1.1] 15.5 13 700 [330.4] 7490520 RCF2417MTAM 18700 [5.5] 14800 [4.3] 3900 [1.1] 15.5 13 700 [330.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGFG: 95 Plus Communicating Modulating Upflow Gas Furnace equipped with Comfort Control, ECM Ratings Outdoor Unit RA1418AJ1 Furnace RGFG-06?MCK? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417HTAM 18200 [5.3] 14100 [4.1] RCF2417MTAM 18200 [5.3] 14100 [4.1] 4100 [1.2] 16 13 575 [271.4] 7490522 4100 [1.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGGE: 90 Plus Communicating Modulating Downflow Gas Furnace equipped with Comfort Control, ECM Ratings Outdoor Unit Furnace Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1430AJ1 RGGE-09?ZCM? RCF3624HTAM 31400 [9.2] 22800 [6.7] 8600 [2.5] 16 13 1025 [483.7] 7491045 RA1430AJ1 RGGE-10?ZCM? RCF3624HTAM 31600 [9.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGGE: 90 Plus Communicating Modulating Downflow Gas Furnace equipped with Comfort Control, ECM Ratings Outdoor Unit Furnace Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1460AC1 RGGE-09?ZCM? RCF6024HTAM 56000 [16.4] 37600 [11.0] 18400 [5.4] 14 11.7 1400 [660.7] 7492572 RA1460AC1 RGGE-12?RCM? RCF6024HTAM 57000 [16.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGJF: 90 Plus Communicating Modulating Horizontal Gas Furnace equipped with Comfort Control, ECM Ratings Outdoor Unit RA1418AJ1 Furnace RGJF-06?MCK? Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RCF2417HTAM 18400 [5.4] 14400 [4.2] RCF2417MTAM 18400 [5.4] 14400 [4.2] 4000 [1.2] 16 13 625 [295.0] 7490524 4000 [1.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) RGJF: 90 Plus Communicating Modulating Horizontal Gas Furnace equipped with Comfort Control, ECM Ratings Outdoor Unit Furnace Indoor Coil Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RA1442AC1 RGJF-06?MCK? RCF4821STAM 41000 [12.0] 29400 [8.6] 11600 [3.4] 14 12.2 1200 [566.3] 7491828 RA1442AC1 RGJF-07?MCK? RCF4821STAM 40500 [11.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) Air Handler Ratings Outdoor Unit RA1418AJ1 RA1424AJ1 RA1430AJ1 RA1436AC1 RA1436AJ1 RA1442AC1 RA1442AJ1 RA1448AC1 Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RBHP-17 18000 [5.3] 11900 [3.5] 6100 [1.8] 15 12.5 600 [283.2] 7493619 RH1P1817STAN 17900 [5.2] 13500 [4.0] 4400 [1.3] 14 12.2 600 [283.
Air Performance Data RA14 Series Performance Data @ AHRI Standard Conditions – Cooling (con’t.) Air Handler Ratings Outdoor Unit RA1448AJ1 RA1460AC1 RA1460AJ1 Total Capacity BTU/H [kW] Net Sensible BTU/H [kW] Net Latent BTU/H [kW] SEER EER Indoor CFM [L/s] AHRI# RBHP-24 45500 [13.3] 29600 [8.7] 15900 [4.7] 15 12.5 1400 [660.7] 7493661 RH1T4821STAN 47000 [13.8] 35600 [10.4] 11400 [3.3] 14.5 12 1575 [743.3] 7492558 RH1T4824STAN 47000 [13.8] 35400 [10.4] 11600 [3.4] 15 12.
Air Guide Specifications RA14 Series GUIDE SPECIFICATIONS General System Description Outdoor-mounted, air-cooled, split-system air conditioner composite base pan unit suitable for ground or rooftop installation. Unit consists of a hermetic compressor, an air-cooled coil, propeller-type condenser fan, suction and legend line service valve, and a control box. Unit will discharge supply air upward as shown on contract drawings. Unit will be used in a refrigeration circuit to match up to a coil unit.
Air Limited Warranty RA14 Series GENERAL TERMS OF LIMITED WARRANTY* Rheem will furnish a replacement for any part of this product which fails in normal use and service within the applicable period stated, in accordance with the terms of the limited warranty. Conditional Parts (Registration Required) ...............................
Air 42 Notes RA14 Series
Air Notes RA14 Series 43
The new degree of comfort.™ In keeping with its policy of continuous progress and product improvement, Rheem reserves the right to make changes without notice. Rheem Heating, Cooling & Water Heating • P.O. Box 17010 Fort Smith, Arkansas 72917 • www.rheem.com Rheem Canada Ltd./Ltée • 125 Edgeware Road, Unit 1 Brampton, Ontario • L6Y 0P5 PRINTED IN U.S.A. 3/15 QG FORM NO. A11-220 REV.