Use and Care Manual
15
WARNING
WARNING
CAUTION
CAUTION
Space must be provided with combustion/ventilation air openings correctly
sized for all other appliances located in the same space as the appliance.
The appliance cover must be securely fastened to prevent it from drawing
air from the appliance room. This is particularly important if the appliance
is in a room with other appliances. Failure to comply with the above could
result in substantial property damage, severe personal injury, or death.
Do not connect the appliance to any heating systems or components that have been previously used for non-potable applications.
Do not introduce toxic chemicals, such as antifreeze or appliance treatments, into the appliance or any piping meant for potable water purposes.
Ensure that all piping and components connected to the appliance are suitable for potable water applications.
Do not use this appliance only for space heating applications.
Failure to follow these instructions could result in property damage, personal injury, or death.
In order for the condensate to properly ow out of the collection system, the appliance must be installed level. Failure to ensure the appliance is
installed level will result in improper appliance operation.
Always take future maintenance into consideration when locating the appliance. If the appliance is located in an installation location with limited
clearances, it may be necessary to remove the appliance from the space to perform maintenance. Failure to consider maintenance when
determining installation location could result in property damage.
6. Clean and ush system when reinstalling an appliance.
NOTE: When installing in a zero clearance location, it may not be possible to read or view some product labeling. It is recommended to make note
of the appliance model and serial number.
NOTE: A combustible door or removable panel is acceptable front
clearance. A 3" minimum clearance must be provided from the appliance
front cover to the removable panel or combustible door.
MINIMUM CLEARANCES FROM COMBUSTIBLE MATERIALS
ㆍ
Hot water pipes – at least 1"(2.5cm) from combustible materials.
ㆍ
Exhaust vent pipe – at least 1"(2.5cm) from combustible materials
▪ C. LEVELING
To save time and money, review the following initial diagnostic steps before calling for service.
▪ D. CLEARANCES FOR SERVICE ACCESS
See Figure 3 and Table 7 for recommended service clearances. If these minimum clearances are not provided, it may not be possible to service
the appliance without removing it from the space.
Figure 3 – Minimum Service Clearances
MINIMUM CLEARANCES
Installation Clearances
from Non-Combustibles /
Combustibles
Recommended Service and Proper Operation
Clearances
Top 18 in. (45.7 cm)
Back 0 in. (0 cm)
Bottom 12 in. (30.45 cm)
Front 24 in. (60.9 cm)
Right Side
3 in. (7.6 cm)
Left Side
Table 7 – Minimum Installation and Service Clearances