PART 7 – GAS PIPING
WARNING
FIRE AND/OR EXPLOSION HAZARD
To avoid serious injury or death, the gas line installation and the gas line inlet pressure test must be done by a licensed professional.
Always match the appliance with the type of gas supplied to the unit (natural gas or LP gas). This appliance must be converted into propane
operation unless specically manufactured for use with propane. Follow Gas Conversion Manual instructions (separate document). Propane
ready appliances have the sufx “LP" after the model serial number.
Failure to ensure the appliance is set to operate on the provided gas supply could result in property damage, personal injury, or death.
1. Gas Pipe Sizing
This information is for reference use only. Refer to gas pipe manufacturer specications for actual delivery capacity. The DOE standard for Natural
Gas is 1100 BTU/ft . Contact the local gas supplier for actual BTU/ft rating.
3
3
▪ A. GAS PIPE SIZING TABLES
Pipe
size
Length (ft)
10'(3m) 20'(6m) 30'(9m) 40'(12m) 50'(15m) 60'(18m) 70'(21m) 80'(24m) 90'(27m) 100'(30m) 125'(37.5m)
3/4˝ 360 247 199 170 151 137 126 117 110 104 92
1˝ 678 466 374 320 284 257 237 220 207 195 173
1-1/4˝ 1390 957 768 657 583 528 486 452 424 400 355
1-1/2˝ 2090 1430 1150 985 873 791 728 677 635 600 532
2" 4020 2760 2220 1900 1680 1520 1400 1300 1220 1160 1020
2 1/2" 6400 4400 3530 3020 2680 2430 2230 2080 1950 1840 1630
3" 11300 7780 6250 5350 4740 4290 3950 3670 3450 3260 2890
4" 23100 15900 12700 10900 9660 8760 8050 7490 7030 6640 5890
Pipe
size
Length (ft)
10'(3m) 20'(6m) 30'(9m) 40'(12m) 50'(15m) 60'(18m) 70'(21m) 80'(24m) 90'(27m) 100'(30m) 125'(37.5m)
1/2˝ 454 312 250 214 190 172 158 147 138 131 116
3/4˝ 949 652 524 448 397 360 331 308 289 273 242
1˝ 1787 1228 986 844 748 678 624 580 544 514 456
1-1/4˝ 3669 2522 2025 1733 1536 1392 1280 1191 1118 1056 936
1-1/2˝ 5497 3778 3034 2597 2302 2085 1919 1785 1675 1582 1402
2" 10588 7277 5844 5001 4433 4016 3695 3437 3225 3046 2700
2 1/2" 16875 11598 9314 7971 7065 6401 5889 5479 5140 4856 4303
3" 29832 20503 16465 14092 12489 11316 10411 9685 9087 8584 7608
4" 43678 30020 24107 20632 18286 16569 15243 14181 13305 12568 11139
Table 13. For 8" WC ~ 10.5" WC initial supply pressure
Table 12. For Less than 8" WC initial supply pressure
Table 14. Maximum Undiluted Propane (LP) Delivery Capacity in Thousands of Btu/H (0.5" WC Pressure Drop)
Maximum Natural Gas Delivery Capacity (0.5" WC Pressure Drop)
Maximum Natural Gas Delivery Capacity (3.0" WC Pressure Drop).
Contact the Gas Supplier for Btu/Cubic Ft. of the Supplied Gas. 1000 BTU/Cubic Ft. is a Typical Value
** For reference only. Please consult gas pipe manufacturer for actual pipe capacities.
Pipe
size
Length (ft)
10'(3m) 20'(6m) 30'(9m) 40'(12m) 50'(15m) 60'(18m) 80'(24m) 100'(30m) 125'(38m) 150'(45m) 175'(53m) 200'(60m) 250'(76m)
1/2˝ 291 200 160 137 122 110 101 94 89 84 74 67 62
3/4˝ 608 418 336 287 255 231 212 197 185 175 155 140 129
1˝ 1150 787 632 541 480 434 400 372 349 330 292 265 243
1-1/4˝ 2350 1620 1300 1110 985 892 821 763 716 677 600 543 500
1-1/2˝ 3520 2420 1940 1660 1480 1340 1230 1140 1070 1010 899 814 749
2˝ 6790 4660 3750 3210 2840 2570 2370 2200 2070 1950 1730 1570 1440