Use and Care Manual

50
How To Enter “Installer Mode"
1. Turn off the power to the Control Panel.
2. Press and hold the button for more than 5 seconds to get into the ‘Installer Mode’.
3. Turn the clockwise or counterclockwise to search to the desired selection in the ‘Installer Mode’.
4. Press to save setting value.
I. INSTALLER MODE
Secondary Show
Primary Show
Primary Show Secondary Show
Description
Parameter Index Step 1 Step 2 Step 3 Default
1:HT
Heating
Temp
Range
HI
121~180°F
(49.5~82°C)
-
180°F
(82°C)
This setting is for changing the heating set temperature
range.
You can change the Highest Set Temperature (HI) and
the Lowest Set Temperature (Lo) by adjusting the num-
bers on the display.
If 2:TR (Outdoor Temperature Reset) is activated (‘on’)
then the settings for 1:HT will be overridden by 2:TR
settings.
Lo
80~120°F
(26~49°C)
-
100°F
(38°C)
2:TR
Outdoor
Temp Reset
oFF - - O
This setting activates or deactivates the Outdoor Tempera-
ture Reset function.
appears and lights up when the Outdoor Tempera-
ture Reset function is activated.
Please check the connection of the outdoor temperature
sensor if is blinking.
You can’t change the heating set temperature manu-
ally while this function is on, because the heating set
temperature is determined by the outdoor temperature
automatically.
on - - -
3:TY
(This
param-
eter doesn’t
show if
2:TR is Off)
Type of
Heating
System
A.Ftb - -
O
120~180°F
(49~82°C)
This section is used to select which type of Heating Sys-
tem is being used.
•There are 6 typical Heating Systems that are available
-Finned Tube Baseboard
-Air Handler
-Cast Iron Baseboard
-Low Mass Radiant Floor
-High Mass Radiant Floor
-Radiator
•For these 6 heating types the low and high temperature
points are
pre-programmed. (See ranges to the left)
* If b.AH is selected, additional steps are needed to be
programmed, see 8:AH
below
•If you would like to use custom low and high temperature
points, select G.CUS and follow the sub menus to set
custom low and high temperature points.
b.AH - -
140~180°F
(60~82°C)
C.Cib - -
100~170°F
(38~76.5°C)
d.LrF - -
80~140°F
(26.5~60°C)
E.rF - -
80~120°F
(26.5~49°C)
F.rAd - -
120~170°F
(49~76.5°C)
G.CUS
HI
121~180°F
(49.5~82°C)
180°F
(82°C)
LO
80~120°F
(26.5~49°C)
100°F
(38°C)
Figure 36 – Installer Mode Screen