RF1P Spec Sheet

Electrical Data
RF1T/RF1P Series
WeatherKing 11
Model/Nominal
Cooling Tons
Voltage Phase Hertz HP [W] RPM Speeds
Circuit
Amps.
Minimum
Circuit
Ampacity
Maximum
Circuit
Protector
RF1P1821 208/230 1 60 1/5 [149] 1075 2 1.5 3 15
RF1P3024 208/230 1 60 1/4 [186] 1075 2 2.5 4 15
RF1P2421 208/230 1 60 1/5 [149] 1075 2 1.5 3 15
RF1P3624 208/230 1 60 1/3 [249] 1075 2 2.5 4 15
RF1T2421 208/230 1 60 1/3 [249] 300-1100 4 1.6 3 15
RF1T3624 208/230 1 60 1/2 [373] 300-1100 4 2.7 4 15
RF1P/RF1T Electrical Data – Blower Motor Only – No Electric Heat
*Blower motors are all single phase motors.
Cooling
Capacity Tons
Heater
kW
(208/240V)
PH/Hz
No. Elements -
kW Per
Type Supply
Circuit
Circuit
Amps.
Motor
Ampacity
Maximum
Circuit
Protection
RF1P/RF1T
18
2.25/3.0 1/60 1-3.0 Single 10.8/12.5 1.5 20/20
3.6/4.8 1/60 1-4.8 Single 17.3/20.0 1.5 25/30
5.4/7.2 1/60 2-3.6 Single 26.0/30.0 1.5 35/40
Model
No.
RXHJ-21B/T05J
RXHJ-21B/T03J
RXHJ-21B/T08J
Minimum
Circuit
Ampacity
24/27
16/18
35/40
RF1P/RF1T
24
RXHJ-21B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 1.5 16/18 20/20
RXHJ-21B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 1.5 24/27 25/30
RXHJ-21B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 1.5 35/40 35/40
RXHJ-21B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 1.5 46/52 50/60
RF1P/RF1T
30
RXHJ-24B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 2.5 17/19 20/20
RXHJ-24B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 2.5 25/29 25/30
RXHJ-24B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 2.5 36/41 40/45
RXHJ-24B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 2.5 47/54 50/60
RF1P/RF1T
36
RXHJ-24B/T03J 2.25/3.0 1/60 1-3.0 Single 10.8/12.5 2.5 17/19 20/20
RXHJ-24B/T05J 3.6/4.8 1/60 1-4.8 Single 17.3/20.0 2.5 25/29 25/30
RXHJ-24B/T08J 5.4/7.2 1/60 2-3.6 Single 26.0/30.0 2.5 36/41 40/45
RXHJ-24B/T10J 7.2/9.6 1/60 2-4.8 Single 34.6/40.0 2.5 47/54 50/60
RF1P/RF1T Electrical Data – with Electric Heat
Installation of the U.L. Listed original equipment manufacturer provided heater kits listed in the table below is recommended for all
auxiliary heating requirements.
• Electric heater BTUH - (heater watts + motor watts) x 3.414 (see airflow table for motor watts.)
• Supply circuit protective devices may be fused or “HACR” type circuit breakers.
• If non-standard fuse size is specified, use next size larger standard fuse size.
• Largest motor load is included in single circuit or circuit 1 of multiple circuits.
• No electrical heating elements are permitted to be used with A Voltage (115V) air handler.
• J voltage (230V) single phase air handler is designed to be used with single or three phase
230 volt electric heaters. In the case of connecting 3 phase power to air handler terminal block
without the heater, bring only two leads to terminal block, cap, insulate and fully secure the third lead.
• Do not use 480 volts electrical heaters on 230 volts air handler.
Electrical Wiring:
Power Wiring
Field wiring must comply with the National Electrical Code
(C.E.C. in Canada) and any applicable local ordinance.
Supply wiring must be 75°C minimum copper conductors only.
See electrical data for product Ampacity rating and Circuit
Protector requirement.
[ ] Designates Metric Conversions
Grounding
This product must be sufficiently grounded in accordance with
National Electrical Code (C.E.C. in Canada) and any applicable
local ordinance.
A grounding lug is provided.