Instruction Manual
5
General Data/Electrical Data
RP14AZ
General Data
GENERAL DATA
MODEL NO.
RP14AZ18**1 RP14AZ18**2 RP14AZ24 RP14AZ30 RP14AZ36 RP14AZ42 RP14AZ48 RP14AZ60
Nominal Tonnage
1.5 1.5 2.0 2.5 3.0 3.5 4.0 5.0
Valve Connections
Liquid Line O.D. – in.
3/8 3/8 3/8 3/8 3/8 3/8 3/8 3/8
Suction Line O.D. – in.
3/4 3/4 3/4 3/4 3/4 7/8 7/8 7/8
Refrigerant (R410A) furnished oz.¹
84 88 88 108 118 148 148 247
Compressor Type
Scroll
Outdoor Coil
Net face area – Outer Coil
10.9 10.9 10.9 14.4 19.5 19.5 19.5 28.4
Net face area – Inner Coil
Tube diameter – in.
0.276 0.276 0.276 0.276 0.276 0.276 0.276 0.375
Number of rows
1 1 1 1 1 1 1 1
Fins per inch
22 22 22 22 22 22 24 20
Outdoor Fan
Diameter – in.
20 20 20 24 24 24 24 26
Number of blades
3 3 3 3 3 3 3 3
Motor hp
1/7 1/7 1/6 1/5 1/5 1/5 1/5 1/5
CFM
2401 2401 2620 3391 4077 4077 4096 4686
RPM
1075 1075 1075 850 850 850 850 850
watts
146 141 145 175 234 222 236 239
Shipping weight – lbs.
157 157 158 196 209 239 245 285
Operating weight – lbs.
150 150 151 189 202 232 238 278
Electrical Data
Line Voltage Data (Volts-Phase-Hz)
208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60 208/230-1-60
Maximum overcurrent protection (amps)²
20 15 20 25 25 35 35 40
Minimum circuit ampacity³
11 11 15 18 21 26 29 31
Compressor
Rated load amps
10 8 11 13 15 20 22 24
Locked rotor amps
46 56 66 71 78 151 127 118
Condenser Fan Motor
Full load amps
0.75 0.75 0.75 1.0 1.0 1.0 1.0 1.0
Locked rotor amps
1.4 1.4 1.5 2.6 2.56 2.56 2.56 2.6
¹
Refrigerant charge sufficient for 15 ft. length of refrigerant lines. For longer line set requirements see the installation instructions for information about set length and additional
refrigerant charge required.
²HACR type circuit breaker of fuse.
³Refer to National Electrical Code manual to determine wire, fuse and disconnect size requirements.